Installation manual

36 
4.5  CHIMNEY SUPPORT INSTALLATION 
Universal Roof Support 
This support has three possible uses: 
1.  It must be used on a roof to support the chimney. 
2.  It may be used on a floor, ceiling or roof above an offset to support the chimney above the 
offset. 
3.  It may be used on a floor, ceiling or roof as a supplementary support. 
For roof support installation, refer to the instructions provided with the support by the chimney 
manufacturer. Many manufacturers will provide the maximum height of chimney that can be 
supported by the support. Make sure you respect those parameters. 
Universal Offset Support 
This support is used to support the chimney above an offset. When the chimney offset is used to 
pass through a wall, this support may be used on the wall to support the chimney. For offset 
support installation, refer to the instructions provided with the support by the chimney 
manufacturer. Many manufacturers will provide the maximum height of chimney that can be 
supported by the support. Make sure you respect those parameters. 
4.6  CHIMNEY CHASE AND MULTIPLE TERMINATIONS 
For the purpose of this manual, a chimney chase is considered a part of the chimney system 
rather than part of a building. The termination must be placed a minimum of 18" (460 mm) above 
the chase. 
For installations where more than one chimney is located in the same chase or within the same 
area, we suggest that their terminations be separated by at least 16" (410 mm) horizontally, and 
18" (460 mm) vertically. This separation is to prevent smoke migrating from one chimney to 
another (see figure 29). 










