Specifications
11
1.3.1  Reduced clearances using shielding 
You may decrease the minimum clearances to combustible materials by installing heat radiation 
shields between the walls or the ceiling and the stove. Those heat radiation shields must be installed 
permanently, and must be made of a heat-resistant or heat-tolerant material. Consult the table below: 
TYPE OF PROTECTION 
Reducing Clearances With 
Shielding 
Sides and 
Rear/Back 
Top 
Sheet metal, a minimum of 0,013" (0,33 mm) spaced out at 
least 7/8" (21 mm) by non-combustible spacers. 
67% 50% 
Ceramic tiles, or an equivalent non-combustible material on 
fire-proof supports spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
50% 33% 
Ceramic tiles, or an equivalent non-combustible material on 
fire-proof supports with a minimum of 0,013" (0,33 mm) 
sheet metal backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
67% 50% 
Brick spaced out at least 7/8" (21 mm) by non-combustible 
spacers. 
50% N/A 
Brick with a minimum of 0,013" (0,33 mm) sheet metal 
backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
67% N/A 
Source: CSA Standard B365-1991, Table 4, Page 27 
Convert specification to R-value: 
  k-factor is given with a required thickness (T) in inches: R=1/k x T 
  C-factor is given: R=1/C 
Example: 
If the floor protector is 4” brick with a C-factor of 1.25 over 1/8” mineral board with 
a k factor of 0.29 the total R-value of the system is: 
  4” brick C=1.25, R=1/1.25=0.8 
  1/8” mineral board K=0.29, R=1/0.29 x 0.125=0.431 
  Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231 
  Total R is greater than 1.0, the system is acceptable. 










