Specifications
9
1.2  POSITIONING THE STOVE 
It is very important to position the wood stove in an area that will favour the most efficient heat 
distribution throughout the house. The stove should therefore be installed in the room where the 
most time is spent, and in the most spacious room possible. Recall that wood stoves produce 
radiating heat, the heat we feel when we are close to a wood stove. A wood stove also functions by 
convection, that is through the displacement of hot air accelerated upwards and its replacement with 
cooler air at the floor level. The stove’s convection effect is facilitated by the installation of a 
blower. 
1.3 CLEARANCES 
Clearances to any combustibles when measured directly from the floor protector to the ceiling must 
be a minimum of 84" (2134 mm). Clearances to any combustibles when measured directly from the  
front of the stove must be a minimum of 48" (1219 mm). The stove must also be placed so as to 
maintain the minimum clearances to combustible walls specified for each type of connector used.  
See Table 1.3 below for all clearance measures 
Table 1.3 Clearances to combustible materials** 
MODELS 
BACK (A) 
Single wall pipe / Double wall
SIDES (B) 
Single wall pipe / Double wall
CORNERS (C) 
Single wall pipe / Double wall
HEIGHT 
(D)* 
Solution 1.6  17’’(432mm) / 12’’(305mm)  15’’(381mm) / 12’’(305mm)  10’’(254mm) / 7’’(178mm) 
*7' / 2,13 
m
Solution 1.8  14’’(356mm) / 6’’(153mm)  12’’(305mm) / 11’’(280mm)  7’’(178mm) / 5’’(127mm) 
*7' / 2,13 
m
Solution 2.3  14’’(356mm) / 6’’(153mm)  12’’(305mm) / 12’’(305mm)  7’’(178mm) / 5’’(127mm) 
*7' / 2,13 
m
Solution 2.9  14’’(356mm) / 6’’(153mm)  14’’(356mm) / 12’’(305mm)  7’’(178mm) / 6’’(153mm) 
*7' / 2,13 
m
* Height, from floor protection to ceiling 
**See Figure 1.3 on the following page 
Note :Clearances to combustible materials for mobile homes are the same. 
You may decrease these clearances by installing heat radiation shields between the walls or the 
ceilin
g
 and the stove. These heat radiation shields must be installed permanentl
y
, and can 
include sheet metal, a rigid non-combustible sheet or a masonr
y
 wall. The installation 
standards of such heat radiation shields are listed on the following page. 
IT IS STRICTLY FORBIDDEN TO PLACE WOOD WITHIN MINIMUM CLEARANCES










