Owner`s manual
11
2.4 The masonry fireplace's draft control system
If the fireplace's draft control system is to remain in the masonry fireplace, it must be locked open for access of
the chimney liner or removed entirely. If you remove draft control system from the masonry hearth, you will
need to install the metal plate (27009), supplied with the owner’s manual kit, indicating that the masonry hearth
has been modified. It must be secured inside the masonry hearth, in a visible place and easy to locate.
2.5 Compliance of a combustible top shelf
To ensure compliance of an existing top shelf or to install any combustible shelf, refer to table below and
Figure 2.5 for a safe installation or to perform changes if necessary. For example, a shelf with a 6’’ depth
(152 mm) must be installed at least 29" (737 mm) above the top of the insert (see Figure 2.5). Different shelf
dimensions are listed in the following table in order to facilitate installation. However, no combustible shelf
can be installed at less than 29" (737 mm) above the top of the insert. If the depth of the shelf is not listed in
the table, add 23" (584 mm) to the depth of your shelf to obtain the safe positioning of your shelf. For
example, for a 9" (229 mm) shelf, the safe positioning would be 32" (724 mm) above the top of the insert
(23" (584 mm) + 9" (813 mm)).
SHELF POSITIONING FOR
SOLUTION 1.8-I AND SOLUTION 2.3-I
MAXIMUM SHELF
DIMENSION (X)
SHELF POSITION
(I)
6" / 152 mm 29" / 737 mm
8" / 203 mm 31" / 787 mm
10" / 254 mm 33" / 838 mm
12" / 305mm 35" / 889 mm