Installation manual
43
TABLE 3 – LIST OF MANDATORY COMPONENTS
CHIMNEY
MANUFACTURER
MANDATORY COMPONENTS TYPE/BRAND
Selkirk
Ventilated roof flashing.
Must have rafter protectors at the roof level if
the chimney is enclosed at the attic level (see
section 4).
Ultra-Temp (UT),
Super Pro (SPR), Super
vent (JSC), Hart &
Cooley (TLC), Sure-
Temp (ST)
Security Chimney
Rafter protector at the roof level if chimney is
enclosed at the attic level (see section 4).
Requires insulated attic radiation shield unless
chimney is enclosed at the attic level.
Requires the use of a 6AW7 (Solid pack 1")
adapter for a ASHT+ of 7".
Requires the use of a 6AW7 and a 7UCA
adapter for the S-2100 of 7".
1" Solid Pack: ASHT+,
2" Solid Pack : S-2100
Simpson Dura-Vent
Ventilated roof flashing.
Rafter protector at the roof level is chimney is
enclosed at the attic level (see section 4).
1" Solid Pack :
Dura Tech
ICC
Ventilated roof flashing.
Rafter protector at the roof level if chimney is
enclosed at the attic level (see section 4).
Excel 2100
American Metal Chimney cannot be enclosed at the attic level.
AC Triple wall HS,
AC Triple wall HSS
WARNING: YOU MUST ALWAYS START WITH AN ANCHOR PLATE OF 6’’ FROM YOUR
FIREPLACE EVEN WHEN YOU USE A 7’’ CHIMNEY. IN THIS CASE, YOU SIMPLY HAVE TO
FIX AN ADAPTER (PART NUMBER 6AW7 IN THE CASE OF AN ASHT+) TO YOUR ANCHOR
PLATE TO USE YOUR 7’’ CHIMNEY. FOR THE S-2100 OF 7”, AN ADDITIONNAL ADAPTER
(PART NUMBER 7UCA) NEEDS TO BE FIXED TO THE 6AW7. SEE SECURITY CHIMNEY
FOR MORE INFORMATION.