Specifications

4
3000775 12.12
1.3 Shipping
The fan is shipped in a corrugated cardboard box. A transport securing device may be attached to the bottom
of the fan to hold the motor and impeller in place. Do not remove the device until the fan is at the installation point.
Do not remove the transport securing device until the fan is being installed on the duct or the roof
curb. The motor shaft could be damaged.
NOTE: All single phase fans are shipped with a capacitor and junction box connected via conduit.
The capacitor is located INSIDE the junction box. Please do not discard.
1.4 Warranty
Complete warranty conditions are available from ENERVEX.
2. Specications
2.1 Dimensions & Capacities
Model RSV 200 RSV 250 RSV 315 RSV 400 RSV 450
Discharge Vertical
Fan Type Centrifugal Impeller
Max. Discharge Velocity FPM 1,729 2,222 2,771 2,752 4,134
Actual Discharge Velocity FPM 2.9 x CFM 1.9 x CFM 1.2 x CFM 5.9 x CFM 1.03 x CFM
Voltage VAC 1 x 120 3 x 200-240 / 3 x 400-480
RPM 1600 1720
Amps A 1.4 2.9 5.8 3.5 / 1.8 6.5 / 3.6
Motor Output hp 0.1 0.2 0.5 1.0 2.0
kW 0.10 0.16 0.35 0.75 1.5
Weight lbs 47 60 88 127 155
kg 18 26 35 58 70
Dimensions A in 11.03 13.20 14.97 16.94 23.23
mm 280 335 380 430 590
B x B in 15.37 19.11 22.85 25.61 25.61
mm 390 485 580 650 650
C x C in 12.22 15.17 18.32 20.69 20.69
mm 310 385 465 525 525
D Ø in 7.88 9.85 12.41 15.76 15.76
mm 200 250 315 400 400
E in 3.15 3.94 4.53 5.12 8.54
mm 80 100 115 130 217
Motor starter required No No No Yes
1)
Yes
1)
Variable speed motor Yes Yes Yes Yes Yes
Temperature Rating Interm 575°F/300°C
Cont. 482°F/250°C
1) Not required if using a VFD