Specifications
7
3001391 06.14
3.4 Termination of Venting System
In order to achieve optimal performance and energy consumption for the RS Fan or GSV Fan, the duct must be installed
as shown below and the distances observed. From the last elbow to the termination point the distance has to be 3 times the
diameteroftheue.Forexampleifyouusing12inue(12X3=36in).Sothedistancefromthelastelbowtothefan
termination point should be 36 inches.
3.5 Installation on Side Wall
• Makesuretheventterminatesushwiththewall.Insertthesteelchimneyadapterandsecureit
safelytothewall.Sealaroundtheedgesoftheadapterange.
• Mark the locations of the wall anchors and predrill holes for them.
• Turn the fan upside-down and lay a bead of hi-temp silicone on the base close to the outer edge
(not shown).
• Open the fan and secure the fan onto the adapter with wall anchors, through the pre drilled holes in
the bottom. Make sure the conduit is located on one of the sides. Never on the upside or downside.
• Seal around the fan base to make sure it is watertight and no water can slip in between the fan and
the adapter. Do not block the 4 drain holes.
3.6 High Temperature Applications
• Ifthefanisusedforapplicationsthatexceeditstemperaturerating,dilutionboltsmustbeused.
• Install the dilution bolts in the outer holes of the fan base.
• Adjusttheheightofthedilutiongapbyadjustingthedilutionbolts,sothetemperatureoftheexhaust
goingthroughthefandoesnotexceedthefan’stemperaturerating.
• Be aware the dilution bolts will have a negative impact on the fan’s actual capacity and a stronger
fan model may be required. For more information, please refer to the installation manual a
accompanying the dilution bolts.