Specifications

11
3001391 06.14
5. Start-up and Conguration
5.1 System Testing
Check the voltage with the motor nameplate rating.
Check that the transport securing device holding the motor shaft and impeller in place has been
removed.
Determine if the impeller is free and has not been subject to misalignment in shipping or installation.
Apply power and check that the impeller is rotating in the direction of the arrow on the side of the top motor
cover. All ENERVEX fans run in a clockwise direction when viewed from the top. Double check
if three phase motor is tested on temporary wiring. Switching any two leads will reverse the rotation.
5.2 Adjusting the Fan Speed
Start all heating appliances connected to the chimney with the fan installed. Set the fan speed control
tothespeedwherenospillageisexperiencedanywhereinthesystem.