Owner`s manual
PRODUCT INFORMATION
External Roof-mounted Power Vent System EuropeanHome.com
5
Fan (PV-WM-146)
Voltage 1 x 120V AC
Amperage 1.2
RPM 1600
Horsepower ⁄
Weight 28 lbs.
Dimension (A) 13.6”
Dimension (B) 11.62”
Dimension (C) 7.88”
Dimension (D) 4.33”
Dimension (E) 6.0”
Dimension (G) 13.78”
SPECIFICATIONS
System Control (PV-GS-CM-ADC 100)
Voltage 1 x 120V AC
Amperage 6.3
Draft Pressure -0.05” w.c.
Weight 2.6 lbs.
Dimension (B) 6.3”
Dimension (A) 9.6”
Dimension (C) 3.5”
Proven Draft Switch (PDS 1)
Temp. Limits -40°F to +190°F
Draft Pressure -0.05” w.c.
Weight 9.6 oz.
Max. Height 3.7”
Max. Width 5.1”
Max. Depth
3.2”
4
3916067 01.13
2.Specications
2.1 Dimensions & Capacities
ADC100 Control
Power supply V 1x120VAC
Amperage A 6.3
Operating temperature °F/°C -4 to 122 / -20 to 50
Control signal mA max. 10
Control relay Max. 120 VAC / 8A
Output VAC 10-120
VDC 0-10
Post Purge Time 0-3 Minutes
Alarm Delay Time 15 Seconds
Dimensions A in/mm 9.6 / 244
B in/mm 6.3 / 160
C in/mm 3.5 / 90
Weight lbs/kg 2.6 / 1.2
Chimney Probe
Dimensions D in/mm 4.25 / 108
E in/mm 3.50 / 89
B
A
C
ADC100
E
D
ADC100
2
3903001 05.12
1. Product Information .............................................................................................................2
2. Specications .............................................................................................................2
3. MechanicalInstallation .............................................................................................................3
4. ElectricalInstallation .............................................................................................................4
5. StartupandConguration .............................................................................................................4
1. Product Information
1.1 Function
Use The PDS 1, Proven Draft Switch, is a fixed position differential pressure switch that is used in conjunction
with ENERVEX’s Mechanical Draft Systems for insufficient draft protection. If an unsafe draft condition
occurs, whether this is caused by mechanical or electrical failure, the switch will shut down the heating
appliance. It is typically used with gas or oil fired appliances where it can be interlocked with
the gas supply valve or the safety or control circuit of the appliance.
Construction The enclosure, the switch housing and the internal switch are made of polycarbonate. The diaphragm is
madeofNBR(silicone),whiletheswitchingcontactismadeinnesilver.
Listings The switch is UL recognized product
1.2Components
Standard
packinglist The PDS shipment contains:
- 1 PDS 1 Differential Pressure Switch
- Duct Kit consisting of stack probe with mounting flange and 6 ft silicone tubing
If other components are shipped, they will appear as separate items on the shipping packing list.
1.3 Warranty
CompletewarrantyconditionsareavailablefromENERVEX,Inc.
2.Specications
2.1Dimensions&Capacities
PDS 1
Maximum Load V 1x120 VAC
Amperage A 3
Range of Operation inWC/Pa .05 to .50/13 to 135
Temperature Limits
o
F/
o
C -40 to +190/ -40 to +88
Max. Pressure PSI/mbar 3 / 207
Wiring Connections 1/4” Solderless Quick Con-
nect Terminals
Pressure Connections Two plastic tubes, outside
diameter of 1/4” (6.0mm)
Weight oz. / kg 9.6 / 0.275
ENERVEX
PDS 1
5.12”
(130 mm)
3.70”
(94 mm)
3.19”
(81 mm)
ENERVEX®
ENERVEX®
ENERVEX®