Owner`s manual

14
INSTALLATION
External Roof-mounted Power Vent System EuropeanHome.com
5
3916067 01.13
3. Mechanical Installation
3.1 Location
The ADC100 Control Unit must be installed indoors.
As shown in the diagram below, the control will be wired directly to a 120/1/60 VAC power supply. The control will also
be connected to the fan, appliance and damper (if used). For detailed wiring information, see Chapter 4.
3.2MountingtheControlUnit
The ADC100 control may be mounted directly to a wall. To mount, remove the cover and locate the (4) mounting
holes. Using the hole-pattern shown below, mount the control using #6 screws. Once it is attached, wire the unit in
accordance with Chapter 4.
ADC100
ENERVEX
ENERVEX
ADC100
PDS1
ADC100
DAMPER
(SOLD
SEPARATELY)
Fig.1
4 MOUNTING HOLES
5.0 in
(127 mm)
8.9 in
(227 mm)
Fig.2
ENERVEX®
5
3916067 01.13
3. Mechanical Installation
3.1 Location
The ADC100 Control Unit must be installed indoors.
As shown in the diagram below, the control will be wired directly to a 120/1/60 VAC power supply. The control will also
be connected to the fan, appliance and damper (if used). For detailed wiring information, see Chapter 4.
3.2MountingtheControlUnit
The ADC100 control may be mounted directly to a wall. To mount, remove the cover and locate the (4) mounting
holes. Using the hole-pattern shown below, mount the control using #6 screws. Once it is attached, wire the unit in
accordance with Chapter 4.
ADC100
ENERVEX
ENERVEX
ADC100
PDS1
ADC100
DAMPER
(SOLD
SEPARATELY)
Fig.1
4 MOUNTING HOLES
5.0 in
(127 mm)
8.9 in
(227 mm)
Fig.2
ENERVEX®
CONFIGURING THE PV-GS-CM-ADC 100
Insulated wire jumpers are connected between terminals 7 and 9, between terminals 8 and 10 and between terminals 16 and
17. Ensure that these jumpers are in place on the PV-GS-CM-ADC 100.
Adjust the fan speed with the ADC100 until your manometer reads -0.05” w.c.
Each of the three DIP switches in the ADC100 should be set as follows:
- 1 (Left) OFF
- 2 (Center) ON
- 3 (Right) ON