Owner`s manual
14
INSTALLATION
External Roof-mounted Power Vent System EuropeanHome.com
5
3916067 01.13
3. Mechanical Installation
3.1 Location
The ADC100 Control Unit must be installed indoors.
As shown in the diagram below, the control will be wired directly to a 120/1/60 VAC power supply. The control will also
be connected to the fan, appliance and damper (if used). For detailed wiring information, see Chapter 4.
3.2MountingtheControlUnit
The ADC100 control may be mounted directly to a wall. To mount, remove the cover and locate the (4) mounting
holes. Using the hole-pattern shown below, mount the control using #6 screws. Once it is attached, wire the unit in
accordance with Chapter 4.
ADC100
ENERVEX
ENERVEX
ADC100
PDS1
ADC100
DAMPER
(SOLD
SEPARATELY)
Fig.1
4 MOUNTING HOLES
5.0 in
(127 mm)
8.9 in
(227 mm)
Fig.2
ENERVEX®
5
3916067 01.13
3. Mechanical Installation
3.1 Location
The ADC100 Control Unit must be installed indoors.
As shown in the diagram below, the control will be wired directly to a 120/1/60 VAC power supply. The control will also
be connected to the fan, appliance and damper (if used). For detailed wiring information, see Chapter 4.
3.2MountingtheControlUnit
The ADC100 control may be mounted directly to a wall. To mount, remove the cover and locate the (4) mounting
holes. Using the hole-pattern shown below, mount the control using #6 screws. Once it is attached, wire the unit in
accordance with Chapter 4.
ADC100
ENERVEX
ENERVEX
ADC100
PDS1
ADC100
DAMPER
(SOLD
SEPARATELY)
Fig.1
4 MOUNTING HOLES
5.0 in
(127 mm)
8.9 in
(227 mm)
Fig.2
ENERVEX®
CONFIGURING THE PV-GS-CM-ADC 100
• Insulated wire jumpers are connected between terminals 7 and 9, between terminals 8 and 10 and between terminals 16 and
17. Ensure that these jumpers are in place on the PV-GS-CM-ADC 100.
• Adjust the fan speed with the ADC100 until your manometer reads -0.05” w.c.
• Each of the three DIP switches in the ADC100 should be set as follows:
- 1 (Left) OFF
- 2 (Center) ON
- 3 (Right) ON