INSTALLATION
External Roof-mounted Power Vent System EuropeanHome.com
INSTALLING the FAN and FAN CONTROLS
The IPVS is ‘built-in-place’ and is the last part of the venting system. The PV-WM-MAS-01 must mount, square and level, to the
inside face of the exterior building wall with the male section projecting through the wall to engage the termination outside.
When installed, it is recommended that the IPVS be oriented as shown below. The IPVS may also be ‘laid on it’s side with the fan
shaft parallel to the ground.
Note:
• The PV-WM-146 fan motor must never be mounted down.
• The male end of the IPVS must connect ONLY to the termination cap.
• The PV-WM-MAS-01 must be mounted with at least 1” clearance to a combustible wall.
The PV-WM-146 fan is then mounted (usually hung from the rafters or oor joists) so as to engage its outlet with the inlet of the
PV-WM-MAS-01. The power venter can be mounted with plumber’s strap or threaded rod with nuts and washers, or it can be
placed on support legs (included). Ensure that the parts are square, plumb and level, fasten the collar of the PV-WM-MAS-01 to the
PV-WM-146 fan with at least 3 screws spaced 120 degrees apart and seal the joint.
Figure 5. ‘Motor Up’ Orientation is Recommended
6.25”
8.00”
6.25”
4.25”
5.00”
5.00”
PV-WM-MAS-01
(Male End)
Fan Outlet
Fan Inlet
PV-WM-FAS-01
(Female End)