Specifications

6.3 Chimney cleaning intervals
It is extremely important to keep the chimney ue clean from creosote and
deposits. Creosote is the major cause of chimney res.
Cleaning intervals depend on the use of the appliance. The more the appli-
ance is used, the more often the chimney ue needs cleaning.
If a replace is used regularly (2-3 times a week), semi-annual chimney
cleaning may be required. If it is used every day, shorter intervals may be
required. Commercial use of wood-red pizza ovens may require chimney
cleaning every 2-3 months.
No matter how much used, a chimney ue serving wood-red appliances
should be cleaned and inspected at least once every year.
NOTE
The chimney should be cleaned by a trained professional.
We recommend using a Certied chimney sweep certied by Chimney Safety Institute of America.
You can nd a Certied Chimney Sweep at www.csia.org or www.ncsg.org
or by calling (317) 837-5362 or (317) 837-1500.6.3 Troubleshooting
Observation Problem Solution
There is no power going to
the fan
The circuit breaker may be o
Fan speed control is o
Bad electrical connections
Check the circuit breaker
Turn fan speed control on
Check and correct problem
There is power to the fan but
it is not operating
Bad electrical connections
The fan speed control’s low voltage
setting is too low
The fan speed control is bad
Check and correct problems with connections. Pay special attention to
the wiring in the junction box
Increase the setting with the plastic screw on the fan speed control’s front
plate
Replace the fan speed control
There is power to the fan but
it hums and does not turn
The motor run capacitor may be
bad.
Creosote may stick
Check capacitor and replace if necessary
Clean fan
The fan seems to work ne,
but there is not enough draft
The fan may be undersized Replace with a larger fan
The fan vibrates The motor shaft may be bent Replace motor
There is airow noise from
the replace opening
The ue is undersized.
The fan is oversized and running
too fast
There is not much to do about it. Try to reduce the rep lace opening
Reduce the fan speed
Mechanical noise can be
heard
Foreign matter may be stuck
Motor bearings may be worn out
Remove matters
Replace bearings
14