User manual
If watt-hours rather than ampere-hours are measured, the 
required overcharge factor will be higher. It is important to 
note that although the battery can deliver at or near its full 
capacity prior to receiving the required overcharge, in order to 
obtain long cycle life, the battery must periodically receive the 
required overcharge. 
Charging can be accomplished by various methods. The 
objective is to drive current through the cell in the direction 
opposite that of discharge. Constant voltage (CV) charging 
is the conventional method for charging lead-acid cells, and 
is acceptable for CYCLON
®
 battery cells. However, constant 
current (CC), taper current and variations thereof can also be 
used.
6.3 Series-parallel CYCLON
®
 Battery Systems 
While there are no theoretical limits on the number of parallel 
strings in a CYCLON battery pack, in practical situations that 
limitation is imposed by (a) whether the application is floating 
or cyclic in nature and (b) the charger design. 
To avoid charge imbalance in a cyclic application, there 
should be no more than five (5) parallel strings. Further, the 
minimum inrush current that the charger should be able to 
provide, assuming single step constant voltage charger is 
5C for a five-string system. If a more sophisticated charge 
algorithm such as the adaptive IUI charge profile is used, 
the minimum inrush can be reduced to 2C for the five-string 
battery pack, allowing 0.4C charge current per string. 
These minimum current values are critical in a cyclic 
environment as the battery is on charge for only limited 
periods of time, creating a potential for significant 
undercharge. Undercharging batteries in cyclic applications 
leads to premature capacity loss and early end of life. 
Batteries in a float application spend most of their time on 
float charge. This allows all strings in a series-parallel system 
to be charged adequately, eliminating the need to restrict the 
number of parallel strings. However, it is still good practice 
to have no more than five parallel strings, regardless of the 
nature of the application.
6.4 Constant Voltage (CV) Charging 
Constant voltage (CV) charging is the most efficient method of 
charging CYCLON battery sealed-lead products. 
Tables 6-1 and 6-2 in the next section on fast charging show 
the recharge times as a function of charge voltage and inrush 
current at 25°C (77°F). The minimum inrush current for single 
voltage level charging is of the order of 0.4C
10 (C10/2.5), and 
one must allow about sixteen (16) hours for a full charge 
under repetitive cycling conditions. If the CV charger that is 
used has an inrush current less than C
10/2.5, then either the 
charge time allowed must be increased or special charge 
algorithms must be evaluated. 
Generally speaking, when the initial current is less than 
C
10/2.5, the charge times must be lengthened by the hourly 
rate at which the charger is limited. In other words, if the 
charger is limited to the C
10/10 rate, then 10 hours should be 
added, giving a total charge time of 26 hours. Using the same 
rule, if the charger is limited to the C
10/5 rate, then 5 hours 
should be added and recharge would require about 21 hours 
instead of 16 hours. 
Note that there are no practical limitations on the maximum 
current imposed by the charging characteristics of the 
CYCLON battery cell under constant voltage charge. 
NOTE: It is important to keep in mind that for cyclic applications the 
charge voltage must be in the 2.45 to 2.50 volts per cell (VPC) 
range. Lowering the voltage to under 2.45 VPC in such an 
application will lead to a rapid loss in capacity, regardless of the 
magnitude of the inrush current.
6.5 Fast Charging or Cyclic Charging 
A fast charge is broadly defined as a method of charge that 
will return the full capacity of a cell in less than four hours. 
However, many applications require a return to a high state 
of charge in one hour or less. Prior to the development of 
CYCLON batteries, commercially available lead-acid batteries 
required charging times of greater than four hours to be 
brought up to a high state of charge. 
Unlike conventional parallel flat plate lead-acid cells, the 
CYCLON battery cell uses a starved electrolyte system where 
the majority of the electrolyte is contained within a highly 
retentive fibrous glass mat separator, creating the starved 
environment necessary for homogeneous gas phase transfer. 
The gassing problem inherent in flooded electrolyte sealed-
lead batteries that utilised alloyed lead is not evident with 
the CYCLON battery system, as the extremely high purity 
of lead minimises the oxygen and hydrogen gas generation 
during overcharge and any oxygen gas generated is able to 
recombine within the sealed cell. The high plate surface area 
of the thin plates used in CYCLON battery cells reduces the 
current density to a level far lower than normally seen in fast 
charge of conventional lead-acid cells, thereby enhancing the 
fast charge capabilities. 
Tables 6-1 and 6-2 display the relationships between charge 
rate and percent of previous discharge capacity returned to 
the cell vs. time at 2.45 volts per cell CV charge. Prior to the 
recharges, the CYCLON battery cell were discharged to 100% 
DOD. 
12
Publication No: EN-CYC-AM-007 - December 2008
www.enersys-emea.com










