User manual
If watt-hours rather than ampere-hours are measured, the
required overcharge factor will be higher. It is important to
note that although the battery can deliver at or near its full
capacity prior to receiving the required overcharge, in order to
obtain long cycle life, the battery must periodically receive the
required overcharge.
Charging can be accomplished by various methods. The
objective is to drive current through the cell in the direction
opposite that of discharge. Constant voltage (CV) charging
is the conventional method for charging lead-acid cells, and
is acceptable for CYCLON
®
battery cells. However, constant
current (CC), taper current and variations thereof can also be
used.
6.3 Series-parallel CYCLON
®
Battery Systems
While there are no theoretical limits on the number of parallel
strings in a CYCLON battery pack, in practical situations that
limitation is imposed by (a) whether the application is floating
or cyclic in nature and (b) the charger design.
To avoid charge imbalance in a cyclic application, there
should be no more than five (5) parallel strings. Further, the
minimum inrush current that the charger should be able to
provide, assuming single step constant voltage charger is
5C for a five-string system. If a more sophisticated charge
algorithm such as the adaptive IUI charge profile is used,
the minimum inrush can be reduced to 2C for the five-string
battery pack, allowing 0.4C charge current per string.
These minimum current values are critical in a cyclic
environment as the battery is on charge for only limited
periods of time, creating a potential for significant
undercharge. Undercharging batteries in cyclic applications
leads to premature capacity loss and early end of life.
Batteries in a float application spend most of their time on
float charge. This allows all strings in a series-parallel system
to be charged adequately, eliminating the need to restrict the
number of parallel strings. However, it is still good practice
to have no more than five parallel strings, regardless of the
nature of the application.
6.4 Constant Voltage (CV) Charging
Constant voltage (CV) charging is the most efficient method of
charging CYCLON battery sealed-lead products.
Tables 6-1 and 6-2 in the next section on fast charging show
the recharge times as a function of charge voltage and inrush
current at 25°C (77°F). The minimum inrush current for single
voltage level charging is of the order of 0.4C
10 (C10/2.5), and
one must allow about sixteen (16) hours for a full charge
under repetitive cycling conditions. If the CV charger that is
used has an inrush current less than C
10/2.5, then either the
charge time allowed must be increased or special charge
algorithms must be evaluated.
Generally speaking, when the initial current is less than
C
10/2.5, the charge times must be lengthened by the hourly
rate at which the charger is limited. In other words, if the
charger is limited to the C
10/10 rate, then 10 hours should be
added, giving a total charge time of 26 hours. Using the same
rule, if the charger is limited to the C
10/5 rate, then 5 hours
should be added and recharge would require about 21 hours
instead of 16 hours.
Note that there are no practical limitations on the maximum
current imposed by the charging characteristics of the
CYCLON battery cell under constant voltage charge.
NOTE: It is important to keep in mind that for cyclic applications the
charge voltage must be in the 2.45 to 2.50 volts per cell (VPC)
range. Lowering the voltage to under 2.45 VPC in such an
application will lead to a rapid loss in capacity, regardless of the
magnitude of the inrush current.
6.5 Fast Charging or Cyclic Charging
A fast charge is broadly defined as a method of charge that
will return the full capacity of a cell in less than four hours.
However, many applications require a return to a high state
of charge in one hour or less. Prior to the development of
CYCLON batteries, commercially available lead-acid batteries
required charging times of greater than four hours to be
brought up to a high state of charge.
Unlike conventional parallel flat plate lead-acid cells, the
CYCLON battery cell uses a starved electrolyte system where
the majority of the electrolyte is contained within a highly
retentive fibrous glass mat separator, creating the starved
environment necessary for homogeneous gas phase transfer.
The gassing problem inherent in flooded electrolyte sealed-
lead batteries that utilised alloyed lead is not evident with
the CYCLON battery system, as the extremely high purity
of lead minimises the oxygen and hydrogen gas generation
during overcharge and any oxygen gas generated is able to
recombine within the sealed cell. The high plate surface area
of the thin plates used in CYCLON battery cells reduces the
current density to a level far lower than normally seen in fast
charge of conventional lead-acid cells, thereby enhancing the
fast charge capabilities.
Tables 6-1 and 6-2 display the relationships between charge
rate and percent of previous discharge capacity returned to
the cell vs. time at 2.45 volts per cell CV charge. Prior to the
recharges, the CYCLON battery cell were discharged to 100%
DOD.
12
Publication No: EN-CYC-AM-007 - December 2008
www.enersys-emea.com










