Information

Lead Wires
Stranded copper wire with insulation meeting UL1015
specifications (Red +, Black -). Standard leads extend 9
inches outside the battery pack. Ends are stripped and
dipped in wax, which must be removed before use.
Standard wire gauges are:
D batteries 18AWG, UL1015
DT batteries 16AWG, UL1015
X batteries 16AWG, UL1015
E batteries 14AWG, UL1015
J batteries 14AWG, UL1015
BC batteries 12AWG, UL1015
Varying lead lengths and gauges are also available;
please specify to your EnerSys
®
Territory Manager or
battery assembler.
Intercell Connections
Standard
D, DT, X and E batteries—welded tin-plated steel
connector
J batteries—soldered, stranded wire
BC batteries—solid copper
For vibration-prone applications
D, DT, X, E and J batteries—soldered, stranded wire
BC batteries—braided copper straps
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 14.8 8.1 5.9 3.4 1.9 1.4 .48 .32 .26 .13
DT cell (4.5Ah) 25.2 15.0 11.2 6.6 3.7 2.6 .85 .55 .45 .24
X cell (5.0Ah) 27.3 17.8 13.2 7.0 3.9 2.8 .96 .61 .50 .26
E cell (8.0Ah) 41.7 26.4 19.0 11.0 6.2 4.4 1.6 1.0 .81 .42
J cell (12.0Ah) 51.7 38.1 29.4 18.0 9.2 6.5 2.3 1.5 1.20 .66
DURATION
Constant current discharge/amps to 1.67Vpc @ 25°C
Products 5 min 10 min 15 min 30 min 60 min 90 min 5 hr 8 hr 10 hr 20 hr
D cell (2.5Ah) 26.4 16.1 11.6 6.7 3.8 2.7 .94 .61 .50 .25
DT cell (4.5Ah) 45.0 28.1 21.0 12.5 7.1 5.1 1.7 1.1 .90 .46
X cell (5.0Ah) 45.4 31.9 23.9 13.9 7.8 5.6 1.9 1.2 1.0 .51
E cell (8.0Ah) 77.8 51.0 35.5 21.1 12.4 8.9 3.1 2.0 1.6 .85
J cell (12.0Ah) 90.4 68.4 53.4 31.6 18.3 13.2 4.7 3.0 2.3 1.3
DURATION
Constant power discharge/watts per cell to 1.67Vpc @ 25°C
Products Cyclic Float Storage & Charge C/5 Cycle life Float life at
discharge 100% DOD 25°C (20°C)
D, DT, X, E & J cell CV 2.40 - 2.45 CV 2.27-2.35 -65°C to +80°C -40°C to -80°C 300 10 years
CC* CC* (15 years)
CHARGING PER CELL
TEMPERATURE RANGE LIFE EXPECTANCY
Charging/Temperature/Life:
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 8 atmospheres
*Users planning to use CC should consult the EnerSys
®
Application Support Department.
UL Recognised Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact your local EnerSys
®
Customer Service Department for details.
CYCLON
®
Battery Single Cell performance specifications
10
Publication No: EN-CYC-SG-004 - June 2014
www.enersys-emea.com
UL - Underwriters Laboratories
AWG - American Wire Gauge