11.0 COMPUTER INTERFACE
11.1 AS400
The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400
computer or equivalent, see figure 21. This facility can also be used with operating system software of other
manufacturers. The function of the pins on the socket are shown below:
Pin
Number
DESCRIPTION FUNCTION NUMBER
8 EDP70 PLUS UPS ON The UPS is supplying the load.
6 RESERVE TO LOAD The reserve AC supply is supplying the load.
9 UTILITY SUPPLY FAIL The AC utility supply to the UPS has failed.
7 BATTERY LOW The battery capacity is at a minimum and the
inverter will shortly shut down and the load will be
automatically transferred to the reserve AC supply.
5 COMMON All the above are connected to common when the
function is true.
Fig.21: EDP 70 Plus Computer Interface Pin Layout