Mode indicator
LED ‘AC in’
blinks red once
per second.
AC input signal is present but
not within required voltage
and frequency borders.
Make sure that the AC input
voltage falls within 185V-
270V and 45Hz-65Hz.
All mode indicator
LEDs ‘inverter on’,
charger on’ and
AC in’ are blinking
red twice per
second (manual
restart needed)
Maximum AC transfer switch
current has been exceeded.
Reduce the AC output load
Mode indicator
LED ‘inverter on’
or ‘charger on’
or ‘AC in’ is red
continuously.
Either the inverter mode,
or the charger mode or the
AC transfer switch has been
disabled using Dashboard.
Enable again using
Dashboard if required.
If only ‘inverter on is
red continuously.
ePRO Combi main switch
is put into charger only’
mode, meaning that the
inverter is disabled.
Output power bar
is red (inverter
mode).
The inverter is overloaded
and will shut down after a
certain time (depending on
the amount of overload)
Reduce the AC output load