User Manual
Page 23
Enerdrive ePRO Inverter / Charger Owners Manual
3. Charge status bar. Gives a rough indication of the charging progress,
see below :
LED 3a 100% full (ready)
LED 3b 80% full
LED 3c 50% full
LED 3d empty
4. Power on, o, charger only switch. See chapter 4.1 for more
explanations.
4.2.1. Error Indications
When the so called mode indicator LEDs are blinking red, an error has
been detected. Each mode indicator LED can either blink red individually,
or combined along with one or more other mode indicator LEDs. There
are ve dierent error indications, each with their own blinking pattern :
One ash in a row Battery related error (too low or too high battery voltage, too low
or too high battery temperature, too high battery ripple voltage,
battery defect)
Two ashes in a row AC overload error (AC load requires too much power from the inverter,
AC output short circuit)
Three ashes in a row High temperature error (ePro Combi shuts down on high temperature)
Four ashes in a row Device error (an error has occurred inside the ePRO Combi. Please
return for service)
Five ashes in a row Charge program error (only for ‘charger on’ indicator LED).
Charge program selection set to Custom, while custom made charge
program contains an error or time-out.