Description The ground switch is an internal relay that automatically connects
AC output Neutral (N) to Protective Earth (PE = chassis) in inverter
mode. This enables the use of a ground fault circuit interrupter
(GFCI) at the AC output of the ePRO Combi. When a non-grounded
(oating-) output is required, this Parameter can be disabled.
Congurable by DIP switch 8 (onEPC 2000-12 to 3500-24 models only) and Dashboard
Parameter AC input fail sensitivity
Value Normal
Description This parameter can be set to Very Low, Low, Normal, High and Very
High. The value of this Parameter decides how fast the ePRO Combi
detects a signal fail at the AC input. The lower settings are resulting
in a slower AC input source
inverter transfer time, while the higher
settings result in the fastest transfer times. The settings Low and Very
Low can be used when the AC input signal is distorted or unstable,
which could be the case when a small generator is used. The settings
High and Very High can be used when the ePRO Combi is connected to
a solid grid or quality generator. The factory setting Normal is a good
compromise, which still results in a fast AC input source inverter
transfer time of less than 5ms, while being reasonably immune
against distorted AC input signals.
Congurable by Dashboard
Parameter Battery type / Charge program
Value AGM