Install Guide

This is for Reference only and local Regulations,
wire size & fusing should be taken into account.
Not to be Copied without permission. Enerdrive Pty Ltd
32mm²
32mm²
16mm²
32mm²
12v or 24v
Start Battery
Ignition
Link
1.5mm²
EN3DC30 Install guide - Dual charger setup.
12v House/Main Battery
Shunt
Fuse - 80Amp
16mm²
Fuse
100Amp
Fuse sized to
suit relay coil
85
30
86
87
Hi Amp Relay/Solenoid
Minimum 100A
Ignition sense for smart alternator vehicles
and Dual DC2DC units.
Also required if start battery has a
secondary charge source
i.e. Solar, AC Charger
32mm²
32mm²
Warning!!
A designated Positive (+) & Negative(-) input cables to
the DC2DC charger MUST be connected to the engine
start battery terminals. Using the vehicle chassis as an
earth return is not permitted.
For late model vehicles fitted with Smart Alternators, the
Negative (-) cable must be attached to thevehicle side
of the alternator sense module.
Failure to follow these instructions will result in spiking
the DC2DC unit and causing the internal input fuses to
blow.
This is not covered under warranty and the fuses are not
field serviceable.
Addendum
Please NOTE:
Vehicles with a Smart alternator,
the Negative cable must be
connected to the vehicle Side
of the Battery Sense Module.
Smart alternator
battery sense
module
Please NOTE:
The High Amp relay on the Input is
required to eliminate excessive loads
on the Start battery once the engine
is turn OFF.
Smart alternator
Negative connection
16mm²
Ignition
Link
1.5mm²
16mm²
Non Regulated
Fix or Folding
Solar Panels
Max 45VOC
(500w)
Warning!! Alternator size
Vehicles running Dual DC2DC should have
a minimum alternator size of 120Amps.
Alternators lower then 120A run the risk of
premature failure due to the high load.
See Warning
Non Regulated
Fix or Folding
Solar Panels
Max 45VOC
(500w)