ePOWER Battery Charger Manual
CAUTION
RISK OF BATTERY AND EQUIPMENT DAMAGE.
Only the Flooded lead-acid can be equalised. Consult your battery manufacturer or read the battery
manual when you try to equalise your batteries.
Disconnect any DC load connected to the battery, as during equalise mode, the charger will produce 15.5V
to the batteries. You must monitor the battery specic gravity throughout the equalisation process to
determine the end of the equalising schedule.
Before setting the equalisation mode on the specic channel, please be sure the channel chosen for
battery equalisation is for a ooded battery type. When the battery equalisation is started, the charger will
automatically fully charge the selected channel rst and follow with 1 hour of equalisation. Check the
battery electrolyte level during the equalisation period. If necessary, rell with distilled water only. All
cells should have similar electrolyte levels. If distilled water is added, batteries must undergo a complete
charge cycle. The charger cannot determine when to terminate the equalisation of the battery. A one hour
time-out is set and this is used as a safety feature to require the user to continually re-activate it as
necessary after checking batteries manually.
During equalisation mode the other two banks are disabled.
Use the following procedure to setup the charger for battery equalisation.
www.enerdrive.com.au Page 31