ePOWER Battery Charger Manual

www.enerdrive.com.au Page 19
Chassis Grounding Connection
DC Output Wiring
Recommended Cable Length, Size And Required Fuse Size
Wire Length Wire Size (mm
2
) - Fuse Size (A)
Model EN31220 EN31240 EN31260
EN32430
1.5 m 6mm
2
– 30A 12mm
2
50A 16mm
2
80A
12mm
2
40A
2.2m 6mm
2
– 30A 16mm
2
50A 25mm
2
80A
16mm
2
40A
6m (Not Recommended) 16mm
2
– 30A 35mm
2
50A 50mm
2
80A
25mm
2
40A
2
120A
2
120A
EN312100
35mm
50mm
70mm
2
120A
WARNING: Correct DC Wiring is Required
The DC wiring used must be of appropriate size. An individual over-current protection device usually
within 20cm of each battery bank is required. A DC disconnect switch is also recommended. Both
devices must be rated for DC voltage and current and be rated to withstand the short circuit current
available from the connected battery bank. Both devices must match with the size of the DC wiring.
The unit is grounded through the ground stud located near the DC Output terminals, refer Section 3 on
Page 10 and 11.
For caravan, RV and other mobile applications the unit should be grounded with a minimum 4mm
conductor.
For marine applications the unit shall be grounded to the main DC negative bus with a separate
conductor the same capacity (size) as the DC positive conductor.