ePOWER Battery Charger Manual

Page 16
Battery Charger Voltage
Battery Type Absorption Float Equalisation
GEL 14.4 V 13.7 V N.A.
AGM 14.6 V 13.6 V N.A.
Flooded 14.4 V 13.3 V 15.5 V (See Note1)
Lithium LiFeP04
Constant 13.9, 14.0, 14.1, 14.2, 14.3,
14.4, 14.5, 14.6 Volts (See Note2)
N.A
Program (Power Supply) Constant 13.3, 13.5, 13.7 Volts (See Note3) N.A
* For 24V model charger multiply above voltages by 2.
** For Concorde branded batteries (lifeline, sun x tender) use ooded setting and consult battery supplier for equalisation
recommendations
Note: Reference your Battery Manual for max charge current as this may dier
The battery charging current rating is based on the battery size. Each battery bank should meet the
minimum Ah rating as shown. If a smaller size battery bank is used, set the current rating to lower value
to match with the battery bank size. Normally, the minimum battery bank capacity is based on twice the
charger current rating.
EN31220 EN31240 EN31260 EN32430
Current
Setting
Battery
Capacity
Current
Setting
Battery
Capacity
Current
Setting
Battery
Capacity
Current
Setting
Battery
Capacity
5A Min 10Ah 5A Min 10Ah 5A Min 10Ah 5A Min 10Ah
10A Min 20Ah 10A Min 20Ah 20A Min 40Ah 10A Min 20Ah
15A Min 30Ah 20A Min 40Ah 40A Min 80Ah 20A Min 30Ah
20A Min 40Ah 40A Min 80Ah 60A Min 120Ah 30A Min 60Ah
Current
Setting
Battery
Capacity
Enerdrive Battery Charger Owners Manual Rev. 5.4
Note 1: Equalisation setting can only be used on ooded battery type selection only. See more details
on Procedure to Equalise the Flooded Battery.
Note 2: Charger will terminate charging when charging current drop to below the set charger
termination value (L setting).
Note 3: Charger is acting as a power supply with selected constant output voltage and preset maximum
output current. With this setting, only Bank 1 can be used, Bank 2 and 3 is disabled.
Battery Bank Size Recommendation
EN312100
40A Min 80Ah
60A Min 120Ah
80A Min 160Ah
100A Min 200Ah