Section INST ALLA TION and OPERA TING INSTR UCTIONS INSTALLA ALLATION OPERATING INSTRUCTIONS for GAS-FIRED INFRA-RED RADIANT TUBE HEATERS ANSI Z83.20b-2004 CSA 2.34b-2004 MOST RECENT EDITION PLACE NEAR HEATING UNIT MODELS ERXL-60, ERXL-80 ERXL-80S, ERXL-100 ERXL-100S, ERXL-125 ERXL-125S ERXL-150 ERXL-150L, ERXL-175 ERXL-175L WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH.
Section 18677 Rev.
01 Section 1 Warnings WARNING FIRE OR EXPLOSION HAZARD Can cause property damage, severe injury or death. 1) Read this manual carefully before installing or servicing this equipment. Improper installation, service or maintenance can cause property damage, injury or death. 2) Check clearances given on the outside of each burner to make sure the product is suitable for your application. 3) Installer must be a trained, experience service technician or representative.
Section 1 Warnings 02 WARNING FAILURE TO FOLLOW THESE INSTRUCTIONS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH: FIRE OR EXPLOSION HAZARD: Combustibles Failure to maintain the specific minimum clearances to combustibles could result in a serious fire hazard. Do not locate flammable or combustible materials within this distance. Do not locate in hazardous atmospheres containing flammable vapors or combustible dust.
03 Section 1 Warnings IMPORTANT FAILURE TO FOLLOW THESE INSTRUCTIONS CAN CAUSE PROPERTY DAMAGE OR PERSONAL INJURY Do not use in an atmosphere containing halogenerated hydrocarbons or other corrosive chemicals. Some compounds in the air can be drawn into the equipment and can cause an accelerated rate of corrosion of some parts of the heat exchanger. The use of such chemical compounds in or near the enclosure should be avoided where a longer life of the burner, tubing and other parts is desirable.
Section TABLE OF CONTENTS WARNINGS & WARRANTY 1 1-3 Read this sections carefully.
05 Section 2 Introduction INTRODUCTION Section 2 Ener-Radiant XL models are low-cost, field assembled infrared heaters that are easy to install and require only minimal maintenance. They are designed to provide years of economical operation and trouble-free service. Checking Shipment Check the shipment against the Bill of Lading for shortages. Also check for external damage to cartons. Note any shortages, and/or external damage to cartons on the Bill of Lading in the presence of the delivery trucker.
Section 3 Planning PLANNING Section 3 The following codes and instructions should be followed when planning the installation of the Ener-Radiant XL heater. In addition to these instructions, the warnings in (Section 1 ) must be carefully adhered to since improper installation may lead to property damage, injury or death. National Standards and Applicable Codes Gas Codes: The type of gas appearing on the nameplate must be the type of gas used.
07 Section 3 Planning Critical Considerations Ener-Radiant XL is a suspended heater. Therefore, its stability, flexibility, and safety are very important. Before starting installation, be sure the system can meet the following requirements. • Maintain specified clearances to combustibles, and safe distance from heat-sensitive material, equipment and work stations.
Section 3 Planning 08 ACCESSORY PARTS LIST Stock Number Description 10371 Thermostat 24 volt 10392 Thermostat 120 volt 17370 Chain Kit 03445 Turbulator 10’ Section 03447 Turbulator 5’ Section 16401 24” Stainless Steel Flexible Gas Connector 18677A Installation Manual / ER3LSeries F106414 180o U-Tube Accessory Kit F106415 90o Elbow Accessory Kit 19021 Vent Adapter 06430 Vent Cap F111751 F111752 F111753 F111754 F111755 Installation kit for 20’ tube heater Installation kit for 30’ tu
09 Section 3 Planning Clearances To Combustibles TABLE 1: Refelctor Type Minimum Clearances to Combustibles (Use figure 1 on page 10 as a Guide) Position ERXL-60 ERXL-80 ERXL-100 ERXL-125 ERXL-150 ERXL-175 Standard Reflector (Horizontal) A B C D 6” 30” 55” 30” 6” 36” 55” 36” 6” 36” 74” 36” 6” 36” 87” 36” 6” 36” 87” 36” 8” 36” 87” 36” 45o Reflector Tilt A B C E F 12” 30” 55” 36” 60” 18” 36” 55” 36” 60” 18” 36” 74” 36” 60” 18” 36” 87” 36” 60” 18” 36” 87” 36” 60” 18” 36” 87” 36” 60” U
Section 3 Planning 10 Clearances To Combustibles FIGURE1: Clearances to Combustibles (Refer to Table 1 on page 9) Standard Reflector 45o Reflector Tilt “U”-Tube, Standard “U”-Tube, Opposite 45o “U”-Tube, Full 45o Front and Back Clearance 18677 Rev.
11 Section 3 Planning Parts List for Packaged Ener-Radiant XL Tube Heaters ITEM STOCK 1 F107400XL DESCRIPTION ERXL-60 NG COMP / 20’ NUMBER REQUIRED X 2 F107401XL ERXL-60 LP COMP / 20’ X 3 F107402XL ERXL-80 NG COMP / 30’ 4 F107403XL ERXL-80 LP COMP / 30’ 5 F107412XL ERXL-80S, NG COMP / 20’ 6 F107413XL ERXL-80S, LP COMP / 20’ 7 F107414XL ERXL-100S, NG COMP /30’ 8 F107415XL ERXL-100S, LP COMP / 30’ 9 F102650XL ERXL-60 NG / BRN & Cont Box 10 F102651XL ERXL-60 LP / BRN & Cont Box
Section 3 Planning 12 Figure “A” - Assembly Model ERXL-60, ERXL-80S Figure “B” - Assembly Model ERXL-80 Figure “C” - Assembly Model ERXL-100S See Page 11 for PARTS LIST 18677 Rev.
13 Section 3 Planning Parts List for Packaged Ener-Radiant XL Tube Heaters ITEM STOCK DESCRIPTION 1 F107404XL ERXL-100 NG COMP / 40’ NUMBER REQUIRED X 2 F107405XL ERXL-100 LP COMP / 40’ X 3 F107406XL ERXL-125 NG COMP / 50’ 4 F107407XL ERXL-125 LP COMP / 50’ 5 F107408XL ERXL-150, NG COMP / 50’ 6 F107409XL ERXL-150, LP COMP / 50’ 7 F107420XL ERXL-175, NG COMP / 50’ 8 F107421XL ERXL-175, LP COMP / 50’ 9 F107416XL ERXL-125S NG COMP / 40’ 10 F107417XL ERXL-125S LP COMP / 40’ 11 F107418XL
Section 3 Planning 14 Figure “D” - Assembly Model ERXL-100, ERXL-125S Figure “E” - Assembly Model ERXL-125, ERXL-150, ERXL-175 Figure “F” - Assembly Model ERXL-150L, 175L See Page 13 for PARTS LIST 18677 Rev.
15 Section 4 Installation & Assembly INSTALLATION & ASSEMBLY FIGURE 2: Section 4 Ener-Radiant XL Overview Key FIGURE 2a: Ener-Radiant XL Model ERXL-60, ERXL-80S, Assembly Overview 20 ft. Exchanger length. 21 ft. - 4 in. Total Heater length. 4 Suspension points as indicated FIGURE 2b: Ener-Radiant XL Model ERXL-80, Assembly Overview 30 ft. Exchanger length. 31 ft - 4 in. Total Heater length. 6 Suspension points as indicated. 18677 Rev.
Section Section 4 Installation & Assembly 16 FIGURE 2c: Ener-Radiant XL Model ERXL-100S, Assembly Overview 30 ft. Exchanger length. 31 ft - 4 in. Total Heater length. 6 Suspension points as indicated. FIGURE 2d: Ener-Radiant XL Model ERXL-100, ERXL-125S 40 ft. Exchanger length. 41 ft - 4 in. Total Heater length. 8 Suspension points as indicated. FIGURE 2e: Ener-Radiant XL Model ERXL-125, ERXL-150, ERXL-175 50 ft. Exchanger length. 51 ft - 4 in. Total Heater length. 10 Suspension points as indicated.
17 Section 4 Installation & Assembly Assemble the heater components as shown in Figures 2a, 2b, 2c, 2d, 2e and 2f. Optional reflector configurations are shown in (Figure 1). Install appropriate suspension hardware, beam clamps, chain or rod at predetermined locations. Adjustment of chain length will provide uniform pitch. Couplings: Tube and tube fittings are connected by wrap-around couplings which clamp by means of a tapered, hammer-driven lock member.
Section Section 4 Installation & Assembly 18 FIGURE 4: Installation of Elbow & Coupling (optional equipment) Elbow package: Stk. #F106415 Elbow Pacakge includes: (1) elbow and (1) coupling. Install elbow into radiant tube sequence where plans indicate a 90o bend (see Figure 4). 90o Elbow Elbow Fitting Dimensions Stk #F106414 U-Tube Package includes: (1) U-tube and (1) coupling. Install U-tube elbow into radinat tube sequnce where plans indicte a 180o bend (see Figure 4).
19 Section 4 Installation & Assembly FIGURE 5: Typical Suspension Details Chain Kit - Stk #17370 One chain kit will suspend one 10 ft. section of tube and one 10 ft. section of reflector. FIGURE 6: Tube & reflector Hanger 18677 Rev.
Section Section 4 Installation & Assembly FIGURE 7: Mounting Flange / Tube Detail 1) Insert tube 06413 into front casting to point (A). 2) Tighten set screws marked (B) until snug. 3) After both set srews are sung, turn each additional 1/4 turn to secure tube in place. FIGURE 8: Burner Box / Transition Tube Detail 18677 Rev.
21 Section 5 Vent / Ducting VENTING / DUCTING Section 5 General Requirements Heater must be vented in accordance with specification ANSI Z223.1 - latest revision. Partial information relating to this specification is provided in this section with regard to size and configurations for venting arrangements ( see Figures 12, 13, 14, 15, 16). For complete information consult ANSI Z223.1 - latest revision and applicable local codes.
Section Section 5 Venting / Ducting Alternative Arrangements / Optional Equipment for Venting Unvented Operation a) Sufficient ventilation must be provided in the amount of 4 CFM per 1,000 BTU/hr. firing rate. b) Refer to ANSI Z223.1 - latest revision, NPFA-54 and local codes for additional information. c) Use of optional outside combustion air is not recommended with unvented heaters due to pressure considerations.
23 Section 5 Vent / Ducting FIGURE 12: Unvented Operation 1) Ventilation equal to 4 CFM per 1,000 BTU/hr. firing rate must be provided in unvented heater installations. 2) For dimensions A “unvented” refer to (Figure 1 -- Minimum Clearances to Combustibles). FIGURE 13a: Single Wall FIGURE 13b: Double Wall Single wall vent run Single wall terminal end Double wall vent rund and Double wall terminal end 18677 Rev.
Section Section 5 Venting / Ducting FIGURE 14: Vertical Venting THIS SPACE IS INTENTIONALLY BLANK 18677 Rev.
25 Section 5 Vent / Ducting FIGURE 15: Common Roof Venting COMMON VENTING - (2) Heaters Model# H = 6 ft. H = 8 ft. H = 15ft. COMMON VENTING - (4) Heaters Model# H = 6 ft. H = 8 ft. H = 15ft.
Section Section 5 Venting / Ducting 16 Outside Combustible Air supply The Ener-Radiant XL heater is approved for installation with an outside air supply system. Some compounds such as halogenated hydrocarbons or other corrosive chemicals in the air can be drawn into the equipment and cause an accelerated rate of corrosion of some of the heater components. The use of such chemical compounds near the enclosure should be avoided.
27 Section 6 Gas Piping GAS PIPING Section 6 Read applicable warnings in (Section 1) before proceeding with Gas Pipe installation. Improper installation may result in property damage, severe injury or death. Meter and service must be large enough to handle all the burners being installed plus any other connected load. the gas line which feed the system must be large enough to supply the required gas with a maximum pressure drop of 1/2” water column.
Section 7 WIRING Wiring 28 Section 7 Heaters are normally controlled by thermostats. Line voltage thermostats are wired directly ( see Feigure 18a), the recommended 24V thermostats use a relay (see Figure 18b). Heaters must be grounded in accordance with the National Electrical Code ANSI/NFPA-70 - latest revision. Heaters may also be controlled with a manual line voltage switch or timer switch in place of the thermostat.
29 Section 7 Wiring FIGURE 19: Wiring of Low Voltage Thermostat and Relay When usung 1 - 2 burners, use SPDT Transformer Relay / Stk. #00172 When using 3 - 4 burners, use DPDT Transformer Relay / Stk. #00183 Wires marked with an asterisk (*) are for use only with the DPDT Transformer Relay. 18677 Rev.
Section 7 FIGURE 20: Wiring 30 Ener-Radiant XL Burner Internal Wiring • If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105o C and 600 volts. • Each burner must be electrically grounded in accordance with the National Electrical Code ANSI / NFPA-70 - latest revision. 18677 Rev.
31 Section 7 Wiring FIGURE 21: Ener-Radiant XL Burner Internal Wiring Ladder Diagram 18677 Rev.
Section 8 Section Operation & Maintenance OPERATION & MAINTENANCE 32 Section 8 Sequence of Operation 1. Turn the thermostat up. When the thermostat calls for heat, blower motor will energize. 2. When the motor approaches nominal running RPM, the air proving switch closes and activates the ignition module. 3. The ignition module then energizes the hot surface igniter for a timed warm-up period (approximately 45 to 60 seconds). 4. After the warm-up period, the gas valve is energized. 5.
33 Section 8 Operation & Maintenance Troubleshooting CAUTION: Before opening the Ener-Radiant XL burner door for any type of service, be sure the gas supply has been shut off at the heater and the electrical cord from the burner box has been unplugged. Blower Motor Fails to Run: 1. Is the thermostat calling for heat? Is there 115V at the burner receptacle? 2. Check blower side door for seal. Check door switch. Replace if necessary. 3. Check blower for obstructions. Replace blower if necessary.
Section 8 Section Operation & Maintenance 34 Honeywell Valve LED Status The ENER-Radiant XL series Tube Heater is equipped with a honeywell Smart Valve. This valve has a built-in diagnostic program, which will assist in troubleshooting in the event of a valve-related problem. The LED or (Light Emitting Diode) is located on the top of the valve as shown in diagram below.
Section 8 Operation & Maintenance Troubleshooting Guide: Ener-Radiant XL 35 18677 Rev.
Section 8 Section Operation & Maintenance 18677 Rev.
37 Section 9 Appendices APPENDIX I: Replacement Parts.
Section 9 Appendices FIGURE 24: Ener-Radiant XL Burner & Control Housing 18677 Rev.
39 Section 9 Appendices APPENDIX II: Engineering Specifications Section 9 The total heating system supplied shall be design certified by the American Gas Association and the Canadian Gas Association. A. Burner & Burner Controls 1. Burners shall be capable of firing with one of the fuel options as specified on the purchase documents: Natural Gas or LP. 2 Burners shall be supplied to fire at any one of the input rates as specified.
Section 9 Appendices APPENDIX II: Section 9 General Specifications for Ener-Radiant XL ERXL-Series Heaters Burner Ratings and Heat Exchanger Lenghts (Natural an LP) Model# 40 Rate (BTU/hr.) Heat Exchanger Length Turbulator Gas pressure at MANIFOLD Natural Gas: 3.5” W.C. LP Gas: 10.5” W.C. 1/2” NPT Gas Connector Size ERXL-60 60,000 20 ft. 10 ft. ERXL-80S 80,000 20 ft. 10 ft. ERXL-80 80,000 30 ft. 10 ft. ERXL-100S 100,000 30 ft. 5 ft. ERXL-100 100,000 40 ft.
Section 18677 Rev.
Section Enerco Technical Products, Inc. 4560 W.160th St.Cleveland, Ohio 44135 Phone: 800-251-0001 www.enerco.com 18677 Rev.