Enecsys Installation and Operation Manual – Version 1.6 –June 6 2012
9
WARNING: Do not connect this or any other Enecsys micro inverter to an
external battery.
WARNING: During normal use, the case temperature of the micro inverter
can exceed 70°C. Install it such that casual contact with the unit is prevented.
WARNING: if connections are not made in the correct order, a voltage may be
present at the exposed wires on the grid connect cable.
The bare wire end of the grid connection cable of each branch circuit should
be connected first to the AC system per the installation instructions.
For installation instructions, see
“6 Installing the micro inverters”.
CAUTION: To reduce the risk of fire, connect only to a circuit provided with
16 amperes maximum branch-circuit overcurrent protection (20A breaker,
16A continuous rating) in accordance with the National Electrical Code,
ANSI/NFPA 70.
1.7 System installation best practices
• Be aware of the anodic index of dissimilar metals used in the installation process.
Note that graphite is a metal.
• Components used to install the PV array should be rated for array conditions and
anticipated installation life.