Installation guide
Installation manual Intelligent Reliable Power
14
© ENECSYS 2010. All rights reserved.
The AC branching cable is attached to distribution connection box. All of the AC connectors are
linked through AC distribution connection blocks to form one continuous AC branch circuit. Each
AC distribution connector block is capable of hosting three AC branch connectors and there
respective Micro-inverters plus one AC Bus Extension cable
1. Using one distribution connector block for every two Micro-inverters connect one AC Bus
Extension connection cable between each of the distribution connector blocks in sequence.
2. Connect the AC lead from each Micro-inverter to the AC distribution connector of the follow-
ing inverter to form the AC branch circuit and so on, until all of the Micro-inverters are con-
nected.
3. Always use an end cap to securely seal any open socket points on the distribution connector.
There must not be any exposed AC socket points as these AC points will be live when the sys-
tem is connected to the utility grid, except when specifically isolated.