Product Manual

4 OF 11
D4. Fluids Permitted / Fluids Not Permitted
DIESEL FUEL at a VISCOSITY from 2 to 5.35 cSt (at a temperature of 37.8)
Minimum Flash point (PM): 55
Description Related Dangers
Gasoline Fire – Explosion
Inflammable Liquids With Pm<55
Fire – Explosion
Liquids With Viscosity>20cst Motor Overload
Water Pump Oxidation
Food Liquids Contamination Of The Same
Corrosive Chemical Products Pump Corrosion, Injury To Persons
Solvents Fire – Explosion, Damage To Gasket Seals
E. MOVING AND TRANSPORT
Given the limited weight and size of the pumps (see overall dimensions), moving the pumps does not require
the use of lifting devices.
The pumps were carefully packed before shipment. Check the packing material on delivery and store in the
dry place.
F. INSTALLATION
F1. Disposing Of the Packing Material
The packing material does not require special precautions, not being in any way dangerous or polluting.
Refer to local regulations for its disposal.
F2. Preliminary Inspection
• Check that the machine has not suffered any damage during transport or storage.
• Clean the inlet and outlet openings, removing any dust or residual packing material.
• Check that the electrical specifications correspond to those shown on the identification plate.
F3. Positioning the Pump
• The pump can be installed in any position (pump axis vertical or horizontal)
• Attach the pump using screws of adequate diameter for the attachment holes provided in the base of the
pump (see the section “OVERALL DIMENSIONS” for their position and dimension).
ATTENTION!
THE MOTORS ARE NOT OF AN ANTI-EXPLOSIVE TYPE.
Do not install them where inflammable vapours can be present.
F4. Connecting the Tubing
PERMITTED
NOT PERMITTED