Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output (for HART devices)
Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
Failsafe mode with user-selectable value: 3.59 to 22.5 mA
Local display
Status signal (in accordance with NAMUR Recommendation NE 107)
Plain text display
Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) or service
interface (CDI)
Status signal (in accordance with NAMUR Recommendation NE 107)
Plain text display
Linearization
The linearization function of the device allows the conversion of the measured value into any unit of length
or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-programmed. Other
tables of up to 32 value pairs can be entered manually or semi-automatically.
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 41 (0x28)
HART specification 6.0
Device description files (DTM,
DD)
Information and files under:
www.endress.com
www.hartcomm.org
HART load
Min. 250 W
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
Level linearized
Distance
Electronic temperature
Relative echo amplitude
Analog output adv. diagnostics
Measured values for SV, TV, FV (second, third and fourth variable)
Level linearized
Distance
Terminal voltage
Electronic temperature
Absolute echo amplitude
Relative echo amplitude
Area of incoupling
Supported functions Burst mode
Additional transmitter status
PROFIBUS PA (in preparation)
Manufacturer ID
17 (0x11)
Ident number 0x1559
Profile version 3.02
GSD file Information and files under:
www.endress.com
www.profibus.org
GSD file version