94 Endress+Hauser
14.3.5 Submenu: Display
Display interval
Navigation System → Display → Display interval
Description Use this function to set the length of time the measured values are displayed if the values
alternate on the local display. This type of change is only generated automatically if
several measured values are specified.
• The Value 1 display - Value 3 display parameters are used to specify which
measured values are shown on the local display.
• The display format of the displayed measured values is specified using the Format
display parameter.
User entry 4 to 20 s
Factory setting 4 s
Format display
Navigation System → Display → Format display
Description Use this function to select how the measured value is shown on the local display. The
display format Measured value or Measured value with bar graph can be configured.
Options • Value
• Value + bar graph
Factory setting Value