Operating Instructions

Table Of Contents
Operating menu and parameter description iTEMP TMT72
82 Endress+Hauser
Navigation System → Device management → Device tag
Description Use this function to enter a unique name for the measuring point so it can be identified
quickly within the plant.
User entry Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /)
Factory setting Depends on the product root and serial number
Mains filter
Navigation System → Device management → Mains filter
Description Use this function to select the mains filter for A/D conversion.
Options 50 Hz
60 Hz
Factory setting 50 Hz
Locking status
Navigation System → Device management → Locking status
Description Displays the device locking status. When write protection is activated, write access to the
parameters is disabled.
User interface Enabled or disabled check box: Locked by hardware
Device reset
Navigation System → Device management → Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options Not active
No action is executed and the user exits the parameter.
To factory defaults
All the parameters are reset to the factory setting.
To delivery settings
All parameters are reset to the order configuration. The order configuration can differ
from the factory setting if customer-specific parameter values were defined when the
device was ordered.
Restart device
The device is restarted but the device configuration remains unchanged.