Operating menu and parameter description iTEMP TMT72
82 Endress+Hauser
Navigation System → Device management → Device tag
Description Use this function to enter a unique name for the measuring point so it can be identified
quickly within the plant.
User entry Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /)
Factory setting Depends on the product root and serial number
Mains filter
Navigation System → Device management → Mains filter
Description Use this function to select the mains filter for A/D conversion.
Options • 50 Hz
• 60 Hz
Factory setting 50 Hz
Locking status
Navigation System → Device management → Locking status
Description Displays the device locking status. When write protection is activated, write access to the
parameters is disabled.
User interface Enabled or disabled check box: Locked by hardware
Device reset
Navigation System → Device management → Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options • Not active
No action is executed and the user exits the parameter.
• To factory defaults
All the parameters are reset to the factory setting.
• To delivery settings
All parameters are reset to the order configuration. The order configuration can differ
from the factory setting if customer-specific parameter values were defined when the
device was ordered.
• Restart device
The device is restarted but the device configuration remains unchanged.