iTEMP TMT72 Operating menu and parameter description
Endress+Hauser 81
HART address
Navigation Application → HART configuration → HART address
Description Use this function to define the HART address of the device.
User entry 0 to 63
Factory setting 0
Additional information The measured value can only be transmitted via the current value if the address is set to
"0". The current is fixed to a value of 4.0 mA for all other addresses (Multidrop mode).
1)
1) Can only be configured in FDT/DTM-based operating tools such as, e.g., Endress+Hauser's FieldCare, DeviceCare, not via the SmartBlue app
however.
No. of preambles
Navigation Application → HART configuration → No. of preambles
Description Use this function to define the number of preambles in the HART telegram.
User entry 5 to 20
Factory setting 5
14.3 Menu: System
14.3.1 Submenu: Device management
HART short tag
Navigation System → Device management → HART short tag
Description Use this function to define a short tag for the measuring point.
User entry Up to 8 alphanumeric characters (letters, numbers and special characters).
Factory setting 8 x '?'
Device tag