Operating menu and parameter description iTEMP TMT72
68 Endress+Hauser
Description Use this function to set a current value for the simulation. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
User entry 3.58 to 23 mA
Factory setting 3.58 mA
Sensor simulation
Navigation Diagnostics → Simulation → Sensor simulation
Description Use this function to enable the simulation of the process variable. The simulation value of
the selected process variable is defined in the Sensor simulation value parameter.
Selection • Off
• On
Factory setting Off
Sensor simulation value
Navigation Diagnostics → Simulation → Sensor simulation value
Description Use this function to enter a simulation value for the process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.
User entry –1.0 · 10
20
to +1.0 · 10
20
°C
Factory setting 0.00 °C
14.1.5 "Diagnostic settings" submenu
Submenu: Properties
Alarm delay
Navigation Diagnostics → Diagnostic settings → Properties → Alarm delay
Description Use this function to set the delay time during which a diagnostics signal is suppressed
before it is output.
User entry 0 to 5 s