Technical data iTEMP TMT72
48 Endress+Hauser
13.4 Performance characteristics
Response time The measured value update depends on the type of sensor and connection method and
moves within the following ranges:
Resistance thermometer (RTD) 1 s
Thermocouples (TC) 1 s
Reference temperature 0.9 s
When recording step responses, it must be taken into account that the times the
internal reference measuring point are added to the specified times where applicable.
Reference operating
conditions
• Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
• Supply voltage: 24 V DC
• 4-wire circuit for resistance adjustment
Maximum measured error In accordance with DIN EN 60770 and the reference conditions specified above. The
measured error data correspond to ±2 s (Gaussian distribution). The data include non-
linearities and repeatability.
Typical
Standard Designation Measuring range Typical measured error (±)
Resistance thermometer (RTD) as per standard Digital value
1)
Value at current
output
IEC 60751:2008 Pt100 (1)
0 to +200 °C (32 to +392 °F)
0.07 °C (0.13 °F) 0.10 °C (0.18 °F)
IEC 60751:2008 Pt1000 (4) 0.05 °C (0.09 °F) 0.08 °C (0.14 °F)
GOST 6651-94 Pt100 (9) 0.06 °C (0.11 °F) 0.09 °C (0.16 °F)
Thermocouples (TC) as per standard Digital value
Value at current
output
IEC 60584, Part 1 Type K (NiCr-Ni) (36)
0 to +800 °C (32 to +1 472 °F)
0.60 °C (1.08 °F) 0.64 °C (1.15 °F)
IEC 60584, Part 1 Type S (PtRh10-Pt) (39) 1.83 °C (3.29 °F) 1.84 °C (3.31 °F)
GOST R8.8585-2001 Type L (NiCr-CuNi) (43) 2.45 °C (4.41 °F) 2.46 °C (4.43 °F)
1)
Measured value transmitted via HART
®
.
Measured error for resistance thermometers (RTD) and resistance transmitters
Standard Designation Measuring range Measured error (±)
Digital
1)
D/A
2)
Maximum
3)
Based on measured value
4)
IEC 60751:2008
Pt100 (1)
–200 to +850 °C
(–328 to +1 562 °F)
≤ 0.1 °C (0.19 °F)
ME = ± (0.05 °C (0.09 °F) +
0.006% * (MV - LRV))
0.03 % (
4.8 µA)
Pt200 (2) ≤ 0.20 °C (0.36 °F)
ME = ± (0.08 °C (0.14 °F) +
0.011% * (MV - LRV))
Pt500 (3) –200 to +510 °C (–328 to +950 °F) ≤ 0.1 °C (0.19 °F)
ME = ± (0.035 °C (0.063 °F)
+ 0.008% * (MV - LRV))
Pt1000 (4) –200 to +250 °C (–328 to +482 °F) ≤ 0.06 °C (0.11 °F)
ME = ± (0.02 °C (0.04 °F) +
0.007% * (MV - LRV))