Product Info
Table Of Contents
iTEMP TMT142
8 Endress+Hauser
Standard Designation Measuring range Typical measured error (±)
GOST 6651-94 Pt100 (9) 0.11 °C (0.2 °F) 0.13 °C (0.23 °F)
Thermocouples (TC) as per standard Digital value
1)
Value at current
output
IEC 60584, Part 1 Type K (NiCr-Ni) (36)
0 to +800 °C (32 to +1 472 °F)
0.41 °C (0.74 °F) 0.47 °C (0.85 °F)
IEC 60584, Part 1 Type S (PtRh10-Pt) (39) 1.83 °C (3.29 °F) 1.84 °C (3.31 °F)
GOST R8.8585-2001 Type L (NiCr-CuNi) (43) 2.45 °C (4.41 °F) 2.46 °C (4.43 °F)
1)
Measured value transmitted via HART
®
.
Measured error for resistance thermometers (RTD) and resistance transmitters
Standard Designation Measuring range Measured error (±)
Digital
1)
D/A
2)
Maximum
3)
Based on measured value
4)
IEC 60751:2008
Pt100 (1)
–200 to +850 °C
(–328 to +1 562 °F)
≤ 0.15 °C (0.27 °F)
ME = ± (0.09 °C (0.16 °F) +
0.006% * (MV - LRV))
0.03 % (
4.8 µA)
Pt200 (2) ≤ 0.25 °C (0.45 °F)
ME = ± (0.13 °C (0.234 °F) +
0.011% * (MV - LRV))
Pt500 (3) –200 to +510 °C (–328 to +950 °F) ≤ 0.25 °C (0.45 °F)
ME = ± (0.19 °C (0.342 °F) +
0.008% * (MV - LRV))
Pt1000 (4) –200 to +500 °C (–328 to +932 °F) ≤ 0.16 °C (0.29 °F)
ME = ± (0.11 °C (0.198 °F) +
0.007% * (MV - LRV))
JIS C1604:1984 Pt100 (5) –200 to +510 °C (–328 to +950 °F) ≤ 0.15 °C (0.27 °F)
ME = ± (0.11 °C (0.198 °F) +
0.006% * (MV - LRV))
GOST 6651-94
Pt50 (8)
–185 to +1 100 °C
(–301 to +2 012 °F)
≤ 0.25 °C (0.45 °F)
ME = ± (0.15 °C (0.27 °F) +
0.008% * (MV - LRV))
Pt100 (9)
–200 to +850 °C
(–328 to +1 562 °F)
≤ 0.15 °C (0.27 °F)
ME = ± (0.09 °C (0.162 °F) +
0.0055% * (MV - LRV))
0.03 % (
4.8 µA)
DIN 43760 IPTS-68
Ni100 (6)
–60 to +250 °C (–76 to +482 °F) ≤ 0.10 °C (0.18 °F)
ME = ± (0.11 °C (0.198 °F) -
0.004% * (MV- LRV))
Ni120 (7)
OIML R84: 2003 /
GOST 6651-2009
Cu50 (10) –180 to +200 °C (–292 to +392 °F) ≤ 0.15 °C (0.27 °F)
ME = ± (0.13 °C (0.234 °F) +
0.006% * (MV - LRV))
Cu100 (11) –180 to +200 °C (–292 to +392 °F) ≤ 0.15 °C (0.27 °F)
ME = ± (0.14 °C (0.252 °F) +
0.003% * (MV - LRV))
Ni100 (12)
–60 to +180 °C (–76 to +356 °F)
≤ 0.15 °C (0.27 °F)
ME = ± (0.16 °C (0.288 °F) -
0.004% * (MV- LRV))
Ni120 (13) ≤ 0.10 °C (0.18 °F)
ME = ± (0.11 °C (0.198 °F) -
0.004% * (MV- LRV))
OIML R84: 2003, GOST
6651-94
Cu50 (14) –50 to +200 °C (–58 to +392 °F) ≤ 0.15 °C (0.27 °F)
ME = ± (0.14 °C (0.252 °F) +
0.004% * (MV - LRV))
Resistance transmitter Resistance Ω 10 to 400 Ω ±50.0mΩ ME = ± 37 mΩ + 0.0032 %
* MW
0.03 % (
4.8 µA)
10 to 2 000 Ω ±300.0mΩ ME = ± 180 mΩ + 0.006 %
* MW
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal.
3) Maximum measured error for the specified measuring range.
4) Deviations from maximum measured error possible due to rounding.