Product Info

iTEMP TMT142
Endress+Hauser 7
Surge current resistance
Lightning surge current D1 (10/350 µs)
Nominal discharge current C1/C2 (8/20 µs)
I
imp
= 1 kA (per wire)
I
n
= 5 kA (per wire)
I
n
= 10 kA (total)
Series resistance per wire 1.8 Ω, tolerance ±5 %
4
+
-
1
2
3
+
-
3
4
S1
S2
-
+
!
+
1
-
Bus connection and
supply voltage
A0041390-EN
 4 Electrical connection of surge arrester
1 Sensor connection
The device must be connected to the potential equalization via the external ground clamp. The
connection between the housing and the local ground must have a minimum cross-section of
4 mm
2
(13 AWG) . All ground connections must be secured tightly.
Performance characteristics
Response time
Resistance thermometer (RTD) and resistance
transmitter (Ω measurement)
≤1 s
Thermocouples (TC) and voltage transmitters (mV) ≤ 1 s
Reference temperature ≤ 1 s
When recording step responses, it must be taken into account that the times of the internal
reference measuring point are added to the specified times where applicable.
Reference operating
conditions
Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
Supply voltage: 24 V DC
4-wire circuit for resistance adjustment
Maximum measured error
In accordance with DIN EN 60770 and the reference conditions specified above. The measured error
data correspond to ±2 s (Gaussian distribution). The data include non-linearities and repeatability.
ME = Measured error
MV = Measured value
LRV = Lower range value of relevant sensor
Typical
Standard Designation Measuring range Typical measured error (±)
Resistance thermometer (RTD) as per standard Digital value
1)
Value at current
output
IEC 60751:2008 Pt100 (1)
0 to +200 °C (32 to +392 °F)
0.11 °C (0.2 °F) 0.13 °C (0.23 °F)
IEC 60751:2008 Pt1000 (4) 0.14 °C (0.25 °F) 0.15 °C (0.27 °F)