Product Info

iTEMP TMT142
Endress+Hauser 5
Overranging Linear increase from 20.0 to 20.5 mA
Failure e.g. sensor failure; sensor short-circuit ≤ 3.6 mA ("low") or ≥ 21 mA ("high"), can be selected
The "high" alarm setting can be set between 21.5 mA and
23 mA, thus providing the flexibility needed to meet the
requirements of various control systems.
Load
Load R
b max.
= (U
b max.
- 11 V) / 0.023 A (current
output).
Ub
36 V
1087
837
250
11 V
0
30.25 V16.75 V
A0041423
Linearization/transmission
behavior
Temperature-linear, resistance-linear, voltage-linear
Network frequency filter
50/60 Hz
Filter
1st order digital filter: 0 to 120 s
Protocol-specific data
Manufacturer ID 17 (0x11)
Device type ID 0x11D1
HART
®
specification 7
Device address in multi-drop mode Software setting addresses 0 to 63
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load min. 250 Ω
HART device variables Measured value for primary value (PV)
Sensor (measured value)
Measured values for SV, TV, QV (secondary, tertiary and quaternary
variable)
SV: device temperature
TV: sensor (measured value)
QV: sensor (measured value)
Supported functions Squawk
Condensed status
Wireless HART data
Minimum starting voltage 11 V
DC
Start-up current 3.58 mA
Start-up time until HART communication is possible 2 s
Start-up time until measured value is available 7 s
Minimum operating voltage 11 V
DC
Multidrop current 4.0 mA
Write protection for device
parameters
Hardware: write protection via DIP switch
Software: user role-based concept (password assignment)