Installation Micropilot FWR30
10 Endress+Hauser
5 Installation
5.1 Mounting the measuring device
5.1.1 Mounting location
Indoors or outdoors.
Installation on vertical pipes
A0040689
Installation with mounting bracket pipe/IBC.
Installation on non-conductive plastic IBC tanks with tubular cage or mesh frame
Installation with "Mounting bracket pipe/IBC".
The mounting bracket pipe/IBC is also suitable for IBC tanks with mesh.
Mounting instructions
Mount the measuring device in a horizontal position so that it is parallel to the tank
ceiling
Otherwise, undesired reflections from the surroundings can cause interference signals
The radar antenna should never be covered by metal objects
If mounting outdoors, do not mount on a depression of the IBC tank
Water can collect and interfere with the measurement. The measuring device may not
stand in water.
Do not mount any objects which may cause interference, such as tank internal fittings,
grids or agitators, below or in the direct vicinity of the radar (see the graphic below)
A0041498