Performance characteristics
Reference operating
conditions
• Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
• Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflector: metal plate with diameter ≥ 1 m (40 in)
• No major interference reflections inside the signal beam
Maximum measured error
Accuracy: ±10 mm (0.39 in) within the entire measuring range
Influence of ambient
temperature
Temperature coefficient: ≤ ± 4 mm (0.16 in) per 10 K
Installation
Mounting location
Indoors or outdoors.
Installation on vertical pipes
A0040689
Installation with mounting bracket pipe/IBC.
Installation on non-conductive plastic IBC tanks with tubular cage or mesh frame
Installation with "Mounting bracket pipe/IBC".
The mounting bracket pipe/IBC is also suitable for IBC tanks with mesh.
Mounting instructions
• Mount the measuring device in a horizontal position so that it is parallel to the tank ceiling
Otherwise, undesired reflections from the surroundings can cause interference signals
• The radar antenna should never be covered by metal objects
• If mounting outdoors, do not mount on a depression of the IBC tank
Water can collect and interfere with the measurement. The measuring device may not stand in
water.
• Do not mount any objects which may cause interference, such as tank internal fittings, grids or
agitators, below or in the direct vicinity of the radar (see the graphic below)