Operation Manual
230V AC +%10 -%20, 50/60Hz or 24V AC %10, 50/60Hz
Max. 5VA
Power connector: 2.5mm²' screw-terminal, Signal connector: 1,5mm² screw-terminal conenction.
EEPROM (minimum 10 years)
Max. 100ohm
12 bit
100ms
Relay : 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.
C/A2 output
ENDA ET2011 PID TEMPERATURE CONTROLLER
Thank you for choosing ENDA ET2011 temperature controller.
TECHNICAL SPECIFICATIONS
Input type
Temperature range
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt10Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
0... 600
0...1300
0... 400
0...1700
0...1700
°C
°C
°C
°C
°C
Accuracy
0,5% (of full scale)
0,5% (of full scale)
1 digit
1 digit
0,5% (of full scale) 1 digit
0,5% (of full scale) 1 digit
0,5% (of full scale) 1 digit
+32... +1112
+32... +2372
+32... +752
+32... +3092
+32... +3092
°F
°F
°F
°F
°F
°C
°F
SSR output
Max 20mA 12Volt (as control output)
SET
°C
SET
ET2011
ENDA
°F
C/A2
SSR
A1
F
PT100 Resistance thermometer
PT100 Resistance thermometer
EN 60751
EN 60751 -200...600 °C
-328...1112 °F
-99.9...300.0 °C
-99.9...543.0 °F
0,5% (of full scale)
1 digit
0,5% (of full scale) 1 digit
Selftune for automatic PID calculation or
manually enter PID parameters if known.
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
Ambient/storage temperature
Max. Relative humidity
0 ... +50 / °C -25... +70°C (with no icing)
Rated pollution degree
According to EN 60529 Front panel : IP65
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gases.
OUTPUTS
Life expectancy for relay
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
EN 61326-1: 2012
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
CONTROL
Control type
Single set-point and alarm control
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power
Adjustable between 0 and 100 . If Pb=0 , On-Off control is selected.% % %
and 250 secondsAdjustable between 1
1 and 50 Adjustable between °C/F
The ratio of power at a set point can be adjusted between 0 and 100% %
HOUSING
Housing type
Suitable for flush-panel mounting according to DIN 43 700.
Dimensions
W77xH35xD71mm
Weight
Approx. 200g (after packing)
Self extinguishing plastics.
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Read this document carefully before using this device. The guarantee will be expired by device demages if you
don't attend to the directions in the user manual. Also we don't accept any compensations for personal injury,
material damage or capital disadvantages.
Relay : 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.
* 77 x 35mm sized.
* Selectable dual setpoint.
* Selectable thermocouple types or PT100 input. (Specify at order).
* Automatic calculation of PID parameters. (SELFTUNE).
* Soft-Start feature.
* Zero point input shift.
* C/A2 Relay output programmable as alarm or control output.
* Selectable SSR control output.
* Selectable heating/cooling control.
* In the case of sensor failure, manual control can be selected.
* CE marked according to European Norms.
ET2011-E-06-201408
Mechanical 30.000.000; Electrical 100.000 operation. 250V AC, 8A and 16A (resistive load).
Relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.