Instructions
EPV242-E-150419
3. / 4
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
i
These parameters are accessible in
models with relay output devices and
specified as "R" in order code.
Used for displaying and configuring the selected parameter value.
Programming
Key
Used for increasing the setpoint value and changing parameters. When held down for a few
seconds, configured numeric value increases faster.
In "Runnig Mode", pressed for 3 seconds continuously, activates or deactivates keylock.
Used for decreasing the setpoint value and changing parameters. When held down for a few
seconds, configured numeric value decreases faster.
Increment
Key
Decrement
Key
SET
ConF
Out1
*
*
tYpE
d.pnt
Opnt
Adr5
bAUd
UPLL
HYSU
dLYU
LOLL
HYSL
Measurement Method
Can be set as , or . Adjusted measurement method indicated by
top of the display LEDs.
AC DC ACdC
Voltage Conversion Rate
Can be adjusted between (/100) and (/100).
If parameter is changed, upper limit value set to the upper scale value,
lower limit value set to the lower scale value and hysteresis values are set to
the 0,1.
1 9999
OtYp
dLyL
*
*
*
*
*
*
*
1TYP
Input Type Selection
If is selected ; By using Max. 100V input (13th and 14th terminals),
is hiden in the menu.
If ; 500V input (12th and 15th terminals),
U100
u.t.r.r.
U500 is selected By using Max.
is hiden in the menu.
If is selected ; By using Max. 500V input (13th and 14th terminals),
value appears in the menu and can be adjusted between 1 and 9999.
u.t.r.r.
u.t.r.r.
u.t.r.r.
SETSET
EPV 242
ENDA
OUT AC DC ACDC
V
0.000
SET
SET
&
&
&
If these keys are pressed and held for 3 seconds, “Programming Mode” is entered or it returns to “Running Mode”. If and keys are pressed
while parameter names are displayed, than it returns to measured value.
u.tr.r.
EPV242 PROGRAMMING DIAGRAM
Decimal Indicator
If device includes relay, type may change according to relay
parameters value.
0
dPnt
If measured value is lower than 10, it can be shown ( ) , ( ) ,
( ) or ( ), (For DC measurements ( ) , ( ) or ( ) ).
measured value between 10 and 100 it can be shown as ( ) ,( ) or
( ), (For DC measurements ( ) or ( ) ).
If measured value between 100 and 1000, it can be shown as ( ) or ( ),
(For DC measurements only ( ) .
as
If ,
0.0 0 0.00
0.0 0 0.00 0.0 0
0.00 0.0
0 0.0 0
0.0 0
0
Samping Time
If 1 ( ) is selected ; sampling time of the measurement is 250ms,
If 2 ( ) is selected, it is 500ms. If 3 ( ) is selected, it is 750ms.
If 4 ( ) is selected, it is 1 second.
1
2 3
4
Device Address
It can be adjusted between - .1 247
B Rateaud
It can be adjusted as , , , , , ,
, and
OFF 1200 2400 4800 9600 19200
38400 57600 115200 .
(*) There are only
parameters in the devices those have no relay.
The and parameters are only in the devices
those have modbus.
(**) AdrS baud
, , , ,1typ u.t.r.r tYPE d.Pnt 0ptn
Out1 Output
It can be adjusted as or If is selected, incase of
alarm, out relay is activated.
n.o. N.c. n.o
Upper Limit Value
If parameter is selected as , can be increased up
to value. If selected as , can be increased up to
100 value. If selected as , can be increased up to 500
value.
This parameter value can not be less than ( - -
).
1typ u.t.r.r.
u.t.r.r. U100
U500
l0ll HY5.l
HY5U
Hysteresis Value for Upper Limit
It can be adjusted between and value. This parameter
can’t be higher than ( ).
When changed, gets the value of .
0 20
- - HY5L
ctrr HY5U 0.1
Upl1 l0l1
Delay Time for Upper Limit Alarm
It can be adjusted between and seconds .0 900
Lower Limit Value
It can be adjusted between lower scale and upper scale that is
specified with parameter.
This parameter can’t be higher than (
) value.
c.tr.r
UPLL - HY5U -
HY5L
Hysteresis Value for Lower Limit
It can be adjusted between and .
This parameter can’t be higher than (
) value. When is
changed, gets the value of .
0 Ctrr /5
-
- ctrr
HY5U 0.1
UPLL
L0LL HY5U
Delay Time for Lower Limit Alarm
It can be adjusted between and seconds.0 900
PROGRAMMING MODE
Powered on device by pressing key. message appears
on display and device reset to default settings.
dPAr
DEFAULT SETTINGS
&
&
01.01
2015
Year
Day.Month
If these keys are pressed and held together, revision
date appears as day, month and year.
SET
0.00
REVISION NUMBER
&
&
SET
While revision information displayed and if one of the pressed key
is released, measured value is displayed again.
Measured Value
Measured current value is
higher than maximum scale.
Measured current value is
lower than minimum scale.
ERROR MESSAGES
Measured Value
L0C
UL0C
0.00
0.00
LOCKING & UNLOCKING KEYPAD
SET
UPLL
LOLL
0.00
0.00
+
By pressing to key for 3 seconds, quick menu is entered.
QUICK MENU
Measured Value
Measured Value
In “Running Mode” , by pressing to key for 3 seconds, keypad locked or unlocked.
SET
SET
SETTING UP THE PARAMETERS
tYPE
dC
ACdC
If key is pressed, the current value of the parameter appears by flashing on the display.
SET
After the setting up the parameters, if set key is pressed again, adjusted parameter
name appears on display.
By using “UP” or “DOWN” navigation keys, selected parameter can be adjusted to
the desired value.
SET
SET