Data Sheet
5. / 5
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Measured value
INPUT REGISTERS
0000d 0x0000 word Read Only–
0001d 0x0001 word
0002d 0x0002 word
–
–
Minimum measured value
Maximum measured value
Read Only
Read Only
Decimal
Hex
OUT Control output condition. (0=OFF; 1=ON).
DISCRATE INPUTS
0000d 0x0000 bit Read Only–
0001d 0x0001 bit –
Alarm control output condition. (0=OFF; 1=ON).
Read Only
Coil
Addresses
Decimal
Hex
Indicator configuration oFF=pr.C5, ON=Pr.Un
COILS
0000d 0x0000 bit R Wd5p.C
0001d 0x0001 bit Cal.t
Calibration type oFF=5.Inp, ON=U.Inp
R W
Holding Register
Addresses
Decimal
Hex
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Input type selection. 0=0-20;1=4-20;2=0-1;3=0-10
Output set value.
* Holding and Input Register parameters, which in integer type is defined as signed integer. Timing parameters are defined as seconds.
(For example, 01:15 is defined as 75 seconds).
HOLDING REGISTERS
MODBUS ADDRESS MAP
0000d 0x0000 word R Wi.tyP
0001d 0x0001 word
0002d 0x0002 word
0003d 0x0003 word
0004d 0x0004 word
0005d 0x0005 word
0006d 0x0006 word
0007d 0x0007 word
0008d 0x0008 word
0009d 0x0009 word
0010d 0x000A word
0011d 0x000B word
0012d 0x000C word
0013d 0x000D word
0014d 0x000E word
0015d 0x000F word
0016d 0x0010 word
0017d 0x0011 word
0018d 0x0012 word
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
RAtE
hold
d.pnt
l.5Cl
H.5Cl
o.5Et
o.Hy5
o.5ta
o.pon
o.ton
o.tof
a.5Et
a.HY5
A.typ
A.5ta
a.pon
a.ton
a.tof
Measurement ranges. 0=Fa5t;1=5.lo1;2=5.lo2;3=5.lo3
Indicator locking parameter. 0=nonE;1=lo;2=HI
Decimal point. 0=x;1=x.x;2=x.xx;3=x.xxx
Scale lower value.
Scale upper value.
Output hysteresis value.
Output condition. (0=OFF,1=Lo, 2=H1)
Alarm set value.
Alarm hysteresis value.
Alarm type. 0=IndE;1=dE;2=band
Alarm condition. 0=OFF, 1=Lo;1=H1;2=b1.H1;3=bo.H1
Required relay-on delay time in order to set output to active state after power-up.
Output relay-on delay time.
Output relay-off delay time.
Required relay-on delay time in order to set alarm output to active state after power-up.
Alarm output relay-on delay time.
Alarm output relay-off delay time.
Holding Register
Addresses
Decimal
Hex
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Holding Register
Addresses
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
Data
Type
Data Content
Parameter
Name
Read / Write
Permission
* MODBUS CONNECTION DIAGRAM
120 Ohm
120 Ohm
Master
Slave - 1
Up to 127 slave devices
can be controlled.
Slave - 2
Slave - 127
A+
B-
A+
B-
A+
B-
A+
B-
Termination should be accomplished by
attaching 120 Ohm resistors to the start
and at the end of the communication line.
* Applies to devices with Modbus function.
EI7041-D-28092021