User manual
Processtemperaturevalueisseen.
Iftimeproportionalcontrolwasselected,isseen.
IfOn-Offcontrolwasselected,andareseen.
Whenthedeviceisenergised,selectedcontrolformisseenonthedisplay.
Ifthedeviceisenergisedwhileholdingkey,contolformchagesandtherelatedmessage
isseenonthedisplay.
Ifkeyispressed,setvalueisseen.
Whenkeyisreleased,processtemperatureisseenagain.
Temperaturedisplay
ATC9311ProgrammingDiagram
Selectingcontrolform
ErrorMessages
Setvalue
Ifthismessageisseen,itmeanstemperaturesesorwasnotdisconnected
orovertemperatureconditionwasoccured.Whenthismessageisseen,
Ifthismessageisseen,itmeansthedevicehasacalibrationerror.Inthis
case,thedeviceshouldbesenttoyourtrader.ortoanearestENDA local
representativeforcalibrationandtesting.Whenthismessageisseen,the
controloutputisdeenergised.
SET
SET
SET
SET
Connectiondiagram
Supplyvoltage
230V AC+%10-%20
24V AC %10±
Ordercode
ATC9311
ATC9311-SSR
ATC9311-24
ATC9311-24-SSR
Controloutput
Relay
Logicoutput
Relay
Logicoutput
ENDA ATC9311isintendedforinstallationincontrolpanels.Makesurethatthedeviceis
usedonlyforintentedpurpose.
Duringaninstallation,allofthecablesthatareconnectedtothedevicemustbefreeof
energy. Thedevicemustbeprotectedagainstinadmisiblehumidity,vibrations,severe
soilingandmakesurethattheoperationtemperatureisnotexceeded. Allinputand
outputlinesthatarenotconnectedtothesupplynetworkmustbelaidoutasshielded
andtwistedcables.Thesecablesshouldnotbeclosetothepowercablesor
components. Theshieldingmustbegroundedontheinstrumentside.
Theelectricalconnectionsmustbecarriedonbya
qualifiedstaffandmustbeaccordingtotherelevantlocallyapplicableregulations.
SENSORINPUT :
Usesuitablecompansationcables.Don'tusejointedcables.
Payattentiontothepolaritiesofthe
thermocouplecablesasshowninthefigurebelow.
TC
-
+
-
+
7
8
230V ACSupply
Mainswitch
Cablesize:1,5mm²
Fuse
F100mA 250V AC
N
L
Fusemust
beconnected!
184-253V AC
50/60Hz 5VA
Supply:
NOTE:
5
4
Logicoutputoftheinstrument ATC9311-SSR
iselectrically insulatedfromthe
internalcircuits. Therefore,whenusinga
groundingthermo-couple,donotconnect
thelogicoutputterminalstotheground.
not
1)Cablesforsupplymustbe
IEC60799orIEC60245conform.
2)Mainswitchshouldbewithin
easyreachandshouldbe
indicated!
Note:
Note:
Thetimeproportionalfunctioncontrolsatemperatureareanearthe
SET value.Outofthistemperaturrangetherelayis“OFF”byoverthe
SET valueor“ON”undertheSET value.
IftheprocessvalueapproximatedtoSET value,the“ON”timefromthe
relaywillbeshortly. Theprocesstemperaturewillbepreventtoswing
orwillbeverysmall.
196°C 200°C
SET-value
Proportionalband8°C
204°C
2%fromscale400°C=8°C
Thefusefortheloadisnotconsidered!
E-mail:info@suran-elektronik.de
Internet:www.suran-elektronik.de
Tel.: +49(0)7451/625617
Fax:+49(0)7451/6250650
SURAN Industrieelektronik
DettingerStr.9/D-72160Horba.N
Terminalconnection
Terminalconnection
INDUSTRIAL ELECTRONICSENDA
ATC9311-230VAC
ANALOGTHERMOSTAT
SN:XXXXXXXXX
1
2
7
6
3
4
5
OUTPUT
250V AC2A
RESISTIVELOAD
230V AC+10%-20%
50/60Hz 5VA
8
+
-
Fe-Const
TC
1
2
7
6
3
4
5
8
+
-
LOGICOUT
12VDC20mA
230V AC+10%-20%
50/60Hz5VA
INDUSTRIAL ELECTRONICSENDA
ATC9311-230VAC
ANALOGTHERMOSTAT
-SSR
SN:XXXXXXXXX
+
-
Fe-Const
TC
2./2 ATC9311-E