Service manual
Encore — Installation and Service Manual 43
Control Panels
Figure 22. Rack Mount Control Panel Installation
Control Panel Grounding
Encore Control panels must be properly grounded before connecting AC
power. Use the ground nut located on the rear of each control panel. See
Figure 23.
1. Attach either a 6 AWG (13.30 mm
2
) wire or a ground strap to lug.
2. Attach lug to ground post.
3. Secure with nut.
Figure 23. Control Panel Ground
8103_00_33r1
44 mm
1.75 in.
432 mm
17 in.
106 mm
4.18 in.
483 mm
19 in.
The 1 rack unit control panels;
BPS, 48B, and XY are 44 mm (1.75 in.)
The 2 rack units control panel,
PMB is 88 mm (3.5 in.)
Control Panel (1 rack-unit)
8103_00_34r0
a 6 AWG (13.30 mm
2
)
Ground wire
Use a Ground strap
Ground lug
Ground nut
or