User`s manual

Serial Communication
SuperDrive 6.10 | 55
6 Serial Communication
Drive Parametrization
Protocol
RS232
RS485
Adam 4520
IC109A
MIW-02
Serial Communication Errors
USB Serial Converter
6.1 Drive Parametrization
The following parameters must be set as below:
Drive
Connection Type
Parameter
Description
SuperDrive Default
CFW-05
RS232/RS485
307
Serial Bit Rate (bit/s)
6 = 9600
308
Drive Address
1
CFW-07
RS232/RS485
308
Drive Address
1
CFW-08
RS232/RS485
308
Drive Address
1
312
Serial
Communication
Protocol
0 = WEGBUS
CFW-09
RS232/RS485
308
Drive Address
1
309
Fieldbus
0 = Disable
312
Serial
Communication
Protocol
0 = WEGBUS
CTW-04
RS232/RS485
65
DI Function
(XC1:37)
1 = operation via
serial (WEGBUS) or
DI
83
Serial WEGBUS
1 = 9600 bps
84
Drive Address
1
85
FieldBus
0 = Inactive
MVW-01
RS232/RS485
308
Drive Address
1
309
Fieldbus
0 = Disable
312
Serial
Communication
Protocol
0 = WEGBUS
SCA-04
RS232/RS485
55
Drive Address
1
48
Serial
Communication
Protocol
0 = 7 bits + 1 parity
bit
SCA-05
RS232/RS485
308
Drive Address
1