User`s manual

Menus
SuperDrive 6.10 | 50
· Type
· Firmware Version
· Nominal Voltage
· Nominal Current
· Tag
4.6.2 Update Parameters to Other Firmware Version
ACCESS
Menu: Tools + Update parameters to other firmware version
Shortcut Key: -
FUNCTION
This tool was designed for updating CFW-09 parameters from the original firmware version, where the
parameters were created, to a different firmware version.
DESCRIPTION
When selecting this tool, the user shall indicate the firmware version to which the parameters of each drive
on the network will be converted.
The conversion is performed and the parameters that were changed are presented to the user. The
parameters that cannot be automatically updated will be loaded with the factory default value. The user will
still be able to change the parameters manually.
The project shall be saved with a different name, so that the existing information is not lost.
Currently, the following versions have the automatic updating function:
· v2.4x
· v2.6x
· v3.1x
· v3.7x
· v4.0x
· v4.4x
Any update between these versions can be automatically performed. Versions that were not listed above
can be manually updated by using this tool.
Example:
· The parameters of a CFW-09 v2.42 were read and stored on the PC.
· The drive was replaced by a CFW-09 v2.64.
· It is desired to transfer the CFW-09 v2.42 parameters stored on the PC to the new CFW-09 v2.64 drive.
· The group of parameters is different since we have different software versions.
· One example is parameter P404. When it is set to 9 on version 2.42 we have 6.0 HP/4.5 kW; when it is
set to 9 on version 2.64 we have 5.5 HP/4.0 kW.
· By using this tool the contents will be converted and it will be possible to transfer them to the drive.