User`s manual

Menus
SuperDrive 6.10 | 32
4. Click [No] for the message "Drive connected?".
5. Follow the menu and manually select the address, drive model, and firmware version. It is not necessary
to indicate the rated voltage and current. It is import to adjust on menu the same firmware version of the
drive. If you do not find the correct option, please, contact WEG. SuperDrivewill not properly work if you
choose a version that is different of the drive version.
6. Click on INSERT in order to add the drive.
7. Click on FINISH when there is no more drives to add.
8. Click on [Online > Communication Setup] and select:
· Serial Port where the modem is connected to.
· Number of trials to retransmit a telegram through serial port after an error is detected. Standard is 5
telegrams.
· Waiting time to receive a telegram. Standard is 100 ms.
· Modem delay time. Standard is 5000 ms.
9. Click on [Online > Monitor Parameters using a Modem].
10. Under Modem window specify:
· Modem command for dialing, the suggested standard is ATDT.
· Phone Number (when using an extension line, add a comma in order to insert an one-second pause).
· Example 1: Phone number 0,33724000. It is a local call.
· Example 2: Phone number 0,0XX4733724000. It is a long distance call, where XX is the phone company
code and the area code is 47.
11. Click on [Dial] and wait for the CD signal (green color).
12. After the phone call is established, click on [Start monitoring].
13. SuperDrive is now monitoring the drive through the phone line.
For more details, see online help, accessing [Help > Topics].
Suggestions for Modems
ATMC - Automação e Comunicação Ltda.
http://www.atmc.com.br
Model MV34.
To display the commands, use the commands "ATE1".
E1 = Eco enabled, ecoa commands to the computer to display what is entered via keypad.
To operate the auto-answer, the manufacturer suggests to apply following commands:
"AT&F&D0&T5X3&K0S2=128S0=2".
AT
informs the modem that an AT command is coming.
&F
loads factory setting.
&D0
ignores DTR signal.
&T5
disables the remote digital loop recognition.
&X3
enables dialing without tone recognition.
&K0
disables the local flow control.
&S2=128
ignores escape sequence.
&S0=2
answers after 2nd ringing (auto answer).
The user must save the configuration in NVRAM by using "AT&W&W1".
&W
saves active profile in profile 0.
&W1
saves active profile in profile 1.
To display what has being saved, enter "AT&V".