6-12 Logging Data
Error Logging
To compile a log of up to three specified error parameters, follow
this procedure:
1. Press the [LOG] key to access the Log Menu.
2. Press [F4] to select “ERROR.”
3. Select a name for the log. Use the shift key and the numeric
keys to enter the desired name.
4. Enter the log message (if desired) to help identify the
particular log. Again, use the shift key and the numeric keys to
enter the desired message.
5. The prompt will ask for the first value logged. Use the [←]
[→] keys to scroll through the available choices, which
include all the parameters on the display (except Time) and on
the Diagnostics menu. Press the appropriate key to select the
first parameter, and then press [ENT].
6. Repeat the procedure for the second and third values logged.
7. The prompt will ask, “Is LOG Circular?” Press [F1] for no, or
[F2] for yes.
8. Enter the time you want to begin logging.
• Press [F1] to accept the displayed time.
• Press [F3] to start the log immediately.
• Follow the steps listed on page 6-6 to enter a new time.
9. Enter the date you want to begin logging.
• Press [F1] to accept the displayed date.
• Press [F3] to start the log today.
• Follow the steps listed on page 6-6 to enter a new date.
The TransPort returns to the beginning of the Log Menu. To exit,
press [EXIT].