User`s manual

Programming Site Data 3-29
December 2003
To Set Up for Active Temperature Inputs:
1. Press [F2] to select IN 1, the supply input.
2. Select [F1] for ACTVE.
3. Enter the temperature for the supply input (base) that
corresponds to a 4 mA signal, then press [ENT].
4. Enter the temperature for the supply input (full) that
corresponds to a 20 mA signal, then press [ENT].
5. Press [F2] to select IN2, the active temperature return input.
6. Select [F1] for ACTVE.
7. Enter the temperature for the return input (base) that
corresponds to a 4 mA signal, then press [ENT].
8. Then enter the temperature for the return input (full) that
corresponds to a 20 mA signal, and press [ENT].
To Set Up for Fixed Temperature Inputs:
1. Press [F2] to select IN1.
2. Press [F2] again to select FIXED.
3. Enter a value for the temperature supply input, and then press
[ENT].
4. Press [F3] to select IN2.
5. Press [F2] to select FIXED.
6. Enter a value for the temperature return input and press
[ENT].