3-10 Programming Site Data
Entering System Parameters (cont.)
8. Choosing Total Energy Units
Use the appropriate feature key to select the units for total energy.
Press [F1] for kBTU - Thousands of British Thermal Units
Press [F2] for MMBTU - Millions of British Thermal Units
Press [F3] for kWHr - Kilowatts-Hours
Press [F4] for Tons - Tons.
9. Choosing Heating or Cooling System
Use the appropriate key to select whether you are making
measurements in a heating or cooling system.
Press [F1] for Cooling, or
Press [F2] for Heating.
10. Selecting Flow Measurement Location
This prompt asks whether you wish to measure flow at the point
of return (where the liquid exits) or at the point of supply (where
the liquid enters).
Press [F1] for return or
Press [F2] for supply.
11. Setting the Date
The next prompt asks you to set the date. You can accept the
currently displayed date by pressing [F1], or correct it as
described below.
a. Press [F2] to edit the date.
b. Use the numeric keys to enter the year. Press [ENT].
c. Use the appropriate feature key to select the desired month.
Use the [] [] keys to view all the options.
d. Use the numeric keys to enter the day, then press [ENT].