User`s manual

Programming Site Data 3-7
December 2003
Entering System Parameters (cont.)
4. Turning the Stopwatch Totalizer On or Off
The Stopwatch Totalizer function enables you to either totalize all
liquid flow continuously, or to manually start and stop totalizing
liquid flow.
Press [F1] to select automatic totalizing, or
Press [F2] to select manual control.
If you select manual control, a”T” appears in the upper right
corner of the screen. To stop the totalizer in manual mode during
operation, press [ON] and the digit 1. To resume totalizing, press
[ON] and the digit 0.
5. Choosing Volumetric Units
To select the units for volumetric flow rate:
a. Use the [] [] keys to view all the options available. See
Table 3-1 for a list of available volumetric units.
b. Press the appropriate feature key to make a selection.
Table 3-1: Volumetric Unit Options
English Volumetric Units Metric Volumetric Units
GAL/S - U.S. Gallons per
Second
L/S- Liter per Second
GAL/M - U.S. Gallons per
Minute
L/M - Liters per Minute
GAL/H - U.S. Gallons per
Hour
L/H - Liters per Hour
MGD - Millions of U.S. Gal-
lons per Day
ML/D - Millions of Liters per
Day
ft
3
/s - Cubic Feet per Second m
3
/s - Cubic Meters per Sec-
ond